Configuration – West Control Solutions KS 94 User Manual

Page 20

Advertising
background image

Allocation of digital signals for set-point processing:

SWi/e

STrac

SdWon

Sw/W2

(Set-point switch-over

from internal to external)

1)

(Bumpless switch-over

to int. set-point with

int./ext. switch-over )

(Effective set-point

offset)

(Switch-over to

set-point w2)

0: only internal set-point

1: W/Wext via front

2: di1=external set-point

3: di2=external set-point

4: di1= internal set-point

5: di2= internal set-point

0: no tracking

2)

1: tracking on

2: di2 = tracking on

3: di12 = tracking on

4: di2 = tracking off

5: di12 = tracking off

0: no offset

2)

1: offset on

2: di1 = offset on

3: di2 = offset on

4: di11 = offset on

5: di1 = offset off

6: di2 = offset off

7: di11 = offset off

0: no W2

2)

1: fixed to W2

2: di1

= W2

3: di2

= W2

4: di12 = W2

5: Timer = W2

6: di1

= W

7: di2

= W

8: di12 = W

Allocation of digital signals for the controller functions:

S A/M

SPI/P

SY2on

SCoff

(Automatic / manual

(manual switch-over)

(3.pnt.stepping controller:

feedback off, otherwise

PI / P switch-over)

(Output of safe

correcting value)

(Switch-off controller)

0: auto/manual via front

1: fixed to manual

2: di1 = manual

3: di2 = manual

4: Backup run

5: di1 = auto

6: di2 = auto

0: PI fixed

2)

1: fixed to P action

2: di1 = P action

3: di2 = P action

4: di1 = PI action

5: di2 = PI action

0: Y no Y2)

2)

1: fixed to Y2

2: di1 = Y2

3: di2 = Y2

4: timer = Y2

5: di1 = Y

6: di2 = Y

0: controller on/off via

front (W = ‘——’)

1: controller fixed to off

2: di1 = controller off

3: di2 = controller off

4: timer= controller off

5: di1= controller on

6: di2= controller on

Allocation of digital signals for the programmer:

(only with programmer configured)

SPrSt

(Signal source for programmer run/stop)

0: Run/Stop: Front

1: Run/Stop: di4

2: Run/Stop: di4 and timer 1

Configuration

Operating instruction KS94

22

More

1) With the programmer configured, switch-over is between internal and external program set-point.

2) Can be switched over via interfaces (e.g. engineering tool; operating data)

Advertising