Configuration – West Control Solutions KS 94 User Manual

Page 23

Advertising
background image

Linearization parameters:

The configuration parameters for linearization are stored as follows.

C.222 xs1

C.223 ys1

value pair 1

C.224 xs2

C.225 ys2

value pair 2

a

Note that the input values

(x-values) must be entered in

ascending order.

(xs1<xs2<xs3...)

C.226 xs3

C.227 ys3

value pair 3

C.228 xs4

C.229 ys4

value pair 4

C.230 xs5

C.231 ys5

value pair 5

C.232 xs6

C.233 ys6

value pair 6

C.234 xs7

C.235 ys7

value pair 7

C.236 xs8

C.237 ys8

value pair 8

The range for these configuration words is within -999 and 9999 or ‘——’ (switched off)!

g

For limiting the number of parameters, these functions can be used only once during pre-processing levels

1 or 2! Linearization segment points which are not required can be switched off by setting ‘——‘.

10.6.2 Signal input 3 / INP3 (ratio variable x2 or auxiliary variable z)

In this case, the signal is configured for ratio variable x2 or auxiliary variable z, provided that option

p.c.b. C is fitted in the controller and the function was selected during controller configuration.

Main configuration:

Selection is only possible with option p.c.b. C provided.

Type

Dp

(Sensor type)

(Number of digits behind the decimal point)

Standard signals:

30: 0 ... 20 mA

31: 4 ... 20 mA

0: no decimal point

1: 1 digit behind the decimal point

2: 2 digits behind the decimal point

3: 3 digits behind decimal point

Additional configuration:

The additional configuration can be used for changing or matching the signal

input default setting for the sensor type.

Select only with type = 31 option p.c.b. C and ratio or auxiliary variable selected.

Fail

(Signal behaviour with sensor error)

1: upscale (X100)

2: downscale (X0)

3: XFail (C.313)

Configuration

25

Operating instruction KS94