OPTICHILL

Chillers

10

Chillers

Technical Manual : 6530166 F 03/2012

General Description

STANDARD FEATURES

Controls

As standard, the

microprocessor controller can provide 8 stages of

capacity control.

Optionally, the controller is designed to provide capabilities for;

Building Management Systems (BMS)

Sequencing (Master/Slave and Run/Standby)

to meet all your system requirements, please specify at order.

For further details, refer to

Controls

, on page 22.

Electrical

A weatherproof electrical power and controls panel is situated at the end of the unit
and contains:

Individual mains power compartments for each
refrigeration circuit

refer to

Interconnecting wiring

,

on page 69

Separate door locking electrical isolation for each mains
compartment

Dedicated bus-bar chamber for connection of incoming 3-
phase and earth mains power supply,

Emergency Stop fitted to controls compartment door

Separate, fully accessible, controls compartment, allowing adjustment of control set
points whilst the unit is operational

Circuit breakers for protection of all major unit components

Phase rotation relay incorporating phase loss protection (compressor module)

The electrical power and control panel is wired to the latest European standards and
codes of practice.

Mains supply is 3 phase and a neutral is not required, refer to

Interconnecting wiring

, on

page 69.

Separate 230V permanent supply is required for the controls and safety features.

Electrical terminals for external evaporator pipework trace heating (230V/500W)
are provided.

CAUTION

A fused and isolated electrical supply of the appropriate phase, frequency and
voltage should be installed.