Installation Data

ELECTRICAL

General

As standard the equipment is designed for 400V, 3 phase, 3 wire 50Hz and a
separate permanent 230V, 1 phase, 50Hz supply, to all relevant IEE regulations,
British standards and IEC requirements

The control voltage to the interlocks is 24V, always size the low voltage interlock and
protection cabling for a maximum voltage drop of 2V

Avoid large voltage drops on cable runs, particularly low voltage wiring

The equipment contains live electrical and moving parts, ISOLATE prior to
maintenance or repair work.

The unit isolators DO NOT isolate the incoming mains supply, but isolate the
individual electrical panels. Isolate REMOTELY the mains incoming supply to the
BUSBAR chamber prior to maintenance or repair work.

CAUTION

ALL work MUST be carried out by technically trained competent personnel.

The Emergency Stop MUST NOT be used to stop the chiller other than in the event
of an emergency.

A fused and isolated electrical supply of the appropriate phase, frequency and
voltage should be installed.

Wires should be capable of carrying the maximum load current under non-fault
conditions at the stipulated voltage.

A separately fused, locally isolated, permanent single phase and neutral supply
MUST BE FITTED for the compressor oil heater, evaporator trace heating and
control circuits, FAILURE to do so will INVALIDATE WARRANTY.

To reduce down time, if possible support the above supply with a UPS.

Ensure correct phase rotation.

Refer also to

Interconnecting wiring

, on page 69.