Optichill ™ chillers, General specification, Chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 42: Mechanical data - high efficiency, Quiet chiller - dq

Advertising
background image

OPTICHILL

Chillers

42

Chillers

Technical Manual : 6530166 V1.6.0 02_2013

General Specification

MECHANICAL DATA - HIGH EFFICIENCY

Quiet Chiller - DQ

OPC500HEDQ10 OPC525HEDQ10 OPC550HEDQ10 OPC600HEDQ10 OPC650HEDQ10

Capacity

Nom Output - Cooling Only

(1)

kW

509.2

533.2

557.1

582.2

607.3

Nom Input - Cooling Only

(1)

kW

185.5

198.5

211.5

223.4

235.3

EER

(2)

2.75

2.69

2.63

2.61

2.58

ESEER

(3)

3.79

3.63

3.49

3.52

3.54

ECA Energy Technology listed

Capacity Steps

%

0, 20, 40, 50, 60, 70, 80, 90, 100

Dimensions - H x W x L

mm

2600 x 2200 x

5675

2600 x 2200 x

5675

2600 x 2200 x

5675

2600 x 2200 x

5675

2600 x 2200 x

5675

Weight - Machine

(4)

kg

6260

6290

6310

6320

6330

Weight - Operating

(4)

kg

6500

6530

6570

6570

6580

Construction - Material / Colour

Base: Plain Galvanised Steel

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)

Evaporator

Shell & Tube

Insulation

Class O / UV Stable

Water Volume

l

233.3

233.3

233.3

233.3

233.3

Total Max. Water Flow

l/s

37.7

37.7

37.7

37.7

37.7

Condenser

Copper Tube / Aluminium Fins

Face Area (Total)

25.8

25.8

25.8

25.8

25.8

Nominal Airflow

m³/s

44.0

44.0

44.0

44.0

44.0

Condenser Fan & Motor

Axial - Sickle Bladed Fan

Quantity

10

10

10

10

10

Diameter

mm

800

800

800

800

800

Speed Setting

rpm

750

750

750

750

750

Head Pressure Fan Speed Control

Microprocessor Controlled EC (Electronically Commutated) Fans

Compressor

Screw - Twin

Quantity

1 + 1

1 + 1

1 + 1

1 + 1

1 + 1

Oil Charge Volume (Total)

l

22 + 22

19 + 22

19 + 19

19 + 19

19 + 19

Oil Type

Ester Oil

Refrigeration

Dual Circuit

Refrigerant Control

Electronic Expansion Valve (EEV)

Refrigerant Pre Charged

R134a

Charge (Total)

kg

100 + 100

105 + 100

105 + 105

105 + 105

105 + 105

Connections

Grooved type Coupling & Pipe Assembly

Water Inlet / Outlet

DN150 PN16

DN150 PN16

DN150 PN16

DN150 PN16

DN150 PN16

Water Drain / Bleed

in

1/2

1/2

1/2

1/2

1/2

Water System

Min. System Water Volume

(5)

l

1750

1832

1915

2001

2087

Max. System Operating Pressure

bar

10

10

10

10

10

OPTIONAL EXTRAS

Water Pump - ac Motor

(1)

In Line Pump - Fixed Speed Motor

Single Head or Run/Standby

Nom External Head Single - Standard

kPa

71

67

64

60

56

Nom External Head Single - Larger

kPa

108

105

101

97

159

Water Pump - Inverter Driven Motor

In Line Pump - Variable Speed Motor

Single Head or Run/Standby

Nom External Head Single - Standard

kPa

124

121

118

71

67

Nom External Head Single - Larger

kPa

124

121

118

159

155

Overall Dimensions with Pump
- H x W x L

(6)

mm

2600 x 2570 x

7075

2600 x 2570 x

7075

2600 x 2570 x

7075

2600 x 2570 x

7075

2600 x 2570 x

7075

(1)

Based on 12/7°C water temperature and 35°C ambient.

(2)

EER

=

Output kW

Input kW

Where:

Output kW

= Chilled Water Cooling duty.

Input kW

= Compressor + Fan input power.

(3)

ESEER, for further details, refer to

ESEER calculations

, on page 27.

(4)

Based on standard unit, for units fitted with options, please contact Airedale. Machine weight includes refrigerant charge; operating weight includes
refrigerant charge and water volume.

(5)

For minimum system volume calculations, refer to

Minimum system water volume calculations

, on page 21.

(6)

-8, -10 & -12 Fan models; pump mounted externally, refer to

Dimensional Data

, on page 56 for details.