Chillers optichill, Controls – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 25

Advertising
background image

Chillers

OPTICHILL

Chillers

25

Technical Manual : 6530166 V1.6.0 02_2013

Controls

STANDARD FEATURES

Unit Remote ON/OFF

Disables/Enables the unit remotely.

Compressor Anti Cycle
Control

Automatic via the Microprocessor.

Compressor Load Limit

Limits the condensing pressure by unloading above 13.2Barg.

Limits the evaporating pressure by unloading at the minimum pressure setpoint, which is,
adjustable depending on system glycol content.

Pump(s) Remote
ON/OFF

Disables/Enables the pump(s) remotely.

Remote Setback
Temperature Setpoint
Switch

A setback setpoint for supply water temperature can be selected to suit summer/winter
conditions or night setback.

Compressor Hours Run

Displays hours run of each compressor.

Password Protection

The control system integrity can be maintained by restricting access with a password
PIN number.

CAUTION

IMPORTANT: To change the PIN number; please contact Airedale at time of order
with the preferred 4 digit number.