Interconnecting wiring, Chillers optichill, Installation data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 69: Chillers, Caution

Advertising
background image

Chillers

OPTICHILL

Chillers

69

Technical Manual : 6530166 V1.6.0 02_2013

Installation Data

INTERCONNECTING WIRING

OPC500 - OPC1100

L1

Mains incoming supply 400V / 3PH / 50Hz

L2

L3

E

L4

N1

Separate Permanent Supply 230V / 1PH +N / 50Hz

E

11

N

External Trace Heating Connections

230V/500W max

502

507

(1) Remote Pump Interlock 24VAC

502

505

(1) Evaporator Pump Water Flow Switch 24VAC

502

504

Unit Remote On/Off 24VAC

502

506

Setback Setpoint Temperature switch

581

580

Non-
Critical
Alarm

Volt Free Common Alarm

582

Volt Free Alarm N/O

Volt Free Alarm N/C

591

590

Critical
Alarm

Volt Free Common Alarm

592

Volt Free Alarm N/O

Volt Free Alarm N/C

RX-/Tx-



RX+/Tx+



GND



Network Connections

CAUTION

(1) MUST be directly wired to the chiller to validate warranty.

Advertising
This manual is related to the following products: