Optichill ™ chillers, Sound data, Chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 38

Advertising
background image

OPTICHILL

Chillers

38

Chillers

Technical Manual : 6530166 V1.6.0 02_2013

Sound Data

GLOBAL CHILLER SOUND LEVEL VALUES - HIGH EFFICIENCY

Standard D Models

Sound
Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

OPC500HED8

Power

100

76

89

92

102

93

85

74

Pressure

@ 10m

68

44

57

60

70

61

53

42

OPC525HED8

Power

98

76

89

91

100

92

85

74

Pressure

@ 10m

66

44

57

59

68

60

53

42

OPC550HED8

Power

95

76

89

89

95

91

85

73

Pressure

@ 10m

63

44

57

57

63

59

53

41

OPC600HED10

Power

97

76

90

91

96

92

87

74

Pressure

@ 10m

65

44

58

59

64

60

55

42

OPC650HED10

Power

98

76

90

92

97

93

88

74

Pressure

@ 10m

66

44

58

60

65

61

56

42

OPC700HED12

Power

97

77

92

95

97

93

87

77

Pressure

@ 10m

64

44

59

62

64

60

54

44

OPC750HED12

Power

97

77

93

97

96

93

85

79

Pressure

@ 10m

64

44

60

64

63

60

52

46

OPC800HED12

Power

97

77

92

98

96

91

85

78

Pressure

@ 10m

64

44

59

65

63

58

52

45

OPC850HED12

Power

96

77

91

99

96

90

84

77

Pressure

@ 10m

63

44

58

66

63

57

51

44

OPC900HED14

Power

98

77

92

101

98

91

86

76

Pressure

@ 10m

65

44

59

68

65

58

53

43

OPC950HED14

Power

99

78

92

102

100

91

87

75

Pressure

@ 10m

66

45

59

69

67

58

54

42

OPC1000HED16

Power

99

78

93

102

99

93

87

77

Pressure

@ 10m

66

45

60

69

66

60

54

44

OPC1100HED16

Power

99

78

93

101

98

94

87

78

Pressure

@ 10m

66

45

60

68

65

61

54

45

Quiet DQ Models

Sound
Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

OPC500HEDQ10

Power

94

82

80

89

94

89

81

69

Pressure

@ 10m

62

50

48

57

62

57

49

37

OPC525HEDQ10

Power

92

82

80

87

92

88

80

69

Pressure

@ 10m

60

50

48

55

60

56

48

37

OPC550HEDQ10

Power

90

82

80

84

88

87

80

68

Pressure

@ 10m

58

50

48

52

56

55

48

36

OPC600HEDQ10

Power

91

82

80

87

89

88

82

68

Pressure

@ 10m

59

50

48

55

57

56

50

36

OPC650HEDQ10

Power

92

82

80

88

90

89

84

69

Pressure

@ 10m

60

50

48

56

58

57

52

37

OPC700HEDQ14

Power

92

83

86

92

89

89

83

73

Pressure

@ 10m

59

50

53

59

56

56

50

40

OPC750HEDQ14

Power

92

83

88

94

89

89

80

75

Pressure

@ 10m

59

50

55

61

56

56

47

42

OPC800HEDQ14

Power

92

83

86

96

89

87

80

74

Pressure

@ 10m

59

50

53

63

56

54

47

41

OPC850HEDQ14

Power

91

83

84

96

88

84

80

72

Pressure

@ 10m

58

50

51

63

55

51

47

39

OPC900HEDQ16

Power

93

84

85

99

91

86

82

71

Pressure

@ 10m

60

51

52

66

58

53

49

38

OPC950HEDQ16

Power

94

84

85

100

92

87

83

68

Pressure

@ 10m

61

51

52

67

59

54

50

35

OPC1000HEDQ18

Power

94

84

85

99

91

89

83

72

Pressure

@ 10m

61

51

52

66

58

56

50

39

OPC1100HEDQ18

Power

94

84

86

99

91

90

83

73

Pressure

@ 10m

61

51

53

66

58

57

50

40

1

dB(A) is the overall sound level, measured on the A scale.

2

All sound data measured at nominal conditions: Water in/out 12/7°C at 35°C ambient.

3

Based on standard unit, for units fitted with optional extras, please contact Airedale.

The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If the equipment is
placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for each side added.