Optichill ™ chillers, General specification, Chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 46: Mechanical data - high efficiency plus, Quiet chiller - dq

Advertising
background image

OPTICHILL

Chillers

46

Chillers

Technical Manual : 6530166 V1.6.0 02_2013

General Specification

MECHANICAL DATA - HIGH EFFICIENCY PLUS

Quiet Chiller - DQ

OPC500HE+DQ12 OPC525HE+DQ12 OPC550HE+DQ12 OPC600HE+DQ12 OPC650HE+DQ12

Capacity

Nom Output - Cooling Only

(1)

kW

538.4

566.6

594.7

622.5

650.2

Nom Input - Cooling Only

(1)

kW

178.8

191.9

205.0

215.1

225.2

EER

(2)

3.01

2.95

2.90

2.89

2.89

ESEER

(3)

4.01

3.84

3.71

3.75

3.78

ECA Energy Technology listed

Capacity Steps

%

0, 20, 40, 50, 60, 70, 80, 90, 100

Dimensions - H x W x L

mm

2600 x 2200 x

7100

2600 x 2200 x

7100

2600 x 2200 x

7100

2600 x 2200 x

7100

2600 x 2200 x

7100

Weight - Machine

(4)

kg

6990

7020

7050

7060

7070

Weight - Operating

(4)

kg

7360

7440

7460

7460

7460

Construction - Material / Colour

Base: Plain Galvanised Steel

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)

Evaporator

Shell & Tube

Insulation

Class O / UV Stable

Water Volume

l

383.7

383.7

383.7

383.7

383.7

Total Max. Water Flow

l/s

55.2

55.2

55.2

55.2

55.2

Condenser

Copper Tube / Aluminium Fins

Face Area (Total)

31.0

31.0

31.0

31.0

31.0

Nominal Airflow

m³/s

52.8

52.8

52.8

52.8

52.8

Condenser Fan & Motor

Axial - Sickle Bladed Fan

Quantity

12

12

12

12

12

Diameter

mm

800

800

800

800

800

Speed Setting

rpm

750

750

750

750

750

Head Pressure Fan Speed Control

Microprocessor Controlled EC (Electronically Commutated) Fans

Compressor

Screw - Twin

Quantity

1 + 1

1 + 1

1 + 1

1 + 1

1 + 1

Oil Charge Volume (Total)

l

22 + 22

19 + 22

19 + 19

19 + 19

19 + 19

Oil Type

Ester Oil

Refrigeration

Dual Circuit

Refrigerant Control

Electronic Expansion Valve (EEV)

Refrigerant Pre Charged

R134a

Charge (Total)

kg

125 + 125

130 + 125

130 + 130

130 + 130

130 + 130

Connections

Grooved type Coupling & Pipe Assembly

Water Inlet / Outlet

DN200 PN16

DN200 PN16

DN200 PN16

DN200 PN16

DN200 PN16

Water Drain / Bleed

in

1/2

1/2

1/2

1/2

1/2

Water System

Min. System Water Volume

(5)

l

1850

1947

2044

2139

2234

Max. System Operating Pressure

bar

10

10

10

10

10

OPTIONAL EXTRAS

Water Pump - ac Motor

(1)

In Line Pump - Fixed Speed Motor

Single Head or Run/Standby

Nom External Head Single - Standard

kPa

86

84

81

79

76

Nom External Head Single - Larger

kPa

123

121

119

116

179

Water Pump - Inverter Driven Motor

In Line Pump - Variable Speed Motor

Single Head or Run/Standby

Nom External Head Single - Standard

kPa

140

137

135

90

87

Nom External Head Single - Larger

kPa

140

137

135

177

175

Overall Dimensions with Pump
- H x W x L

(6)

mm

2600 x 2570 x

8500

2600 x 2570 x

8500

2600 x 2570 x

8500

2600 x 2570 x

8500

2600 x 2570 x

8500

(1)

Based on 12/7°C water temperature and 35°C ambient.

(2)

EER

=

Output kW

Input kW

Where:

Output kW

= Chilled Water Cooling duty.

Input kW

= Compressor + Fan input power.

(3)

ESEER, for further details, refer to

ESEER calculations

, on page 27.

(4)

Based on standard unit, for units fitted with options, please contact Airedale. Machine weight includes refrigerant charge; operating weight includes
refrigerant charge and water volume.

(5)

For minimum system volume calculations, refer to

Minimum system water volume calculations

, on page 21.

(6)

-8, -10 & -12 Fan models; pump mounted externally, refer to

Dimensional Data

, on page 56 for details.