Optichill ™ chillers, General specification, Chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 46: Mechanical data - high efficiency plus, Quiet chiller - dq
![background image](/manuals/370934/46/background.png)
OPTICHILL
™
Chillers
46
Chillers
Technical Manual : 6530166 V1.6.0 02_2013
General Specification
MECHANICAL DATA - HIGH EFFICIENCY PLUS
Quiet Chiller - DQ
OPC500HE+DQ12 OPC525HE+DQ12 OPC550HE+DQ12 OPC600HE+DQ12 OPC650HE+DQ12
Capacity
Nom Output - Cooling Only
(1)
kW
538.4
566.6
594.7
622.5
650.2
Nom Input - Cooling Only
(1)
kW
178.8
191.9
205.0
215.1
225.2
EER
(2)
3.01
2.95
2.90
2.89
2.89
ESEER
(3)
4.01
3.84
3.71
3.75
3.78
ECA Energy Technology listed
Capacity Steps
%
0, 20, 40, 50, 60, 70, 80, 90, 100
Dimensions - H x W x L
mm
2600 x 2200 x
7100
2600 x 2200 x
7100
2600 x 2200 x
7100
2600 x 2200 x
7100
2600 x 2200 x
7100
Weight - Machine
(4)
kg
6990
7020
7050
7060
7070
Weight - Operating
(4)
kg
7360
7440
7460
7460
7460
Construction - Material / Colour
Base: Plain Galvanised Steel
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)
Evaporator
Shell & Tube
Insulation
Class O / UV Stable
Water Volume
l
383.7
383.7
383.7
383.7
383.7
Total Max. Water Flow
l/s
55.2
55.2
55.2
55.2
55.2
Condenser
Copper Tube / Aluminium Fins
Face Area (Total)
m²
31.0
31.0
31.0
31.0
31.0
Nominal Airflow
m³/s
52.8
52.8
52.8
52.8
52.8
Condenser Fan & Motor
Axial - Sickle Bladed Fan
Quantity
12
12
12
12
12
Diameter
mm
800
800
800
800
800
Speed Setting
rpm
750
750
750
750
750
Head Pressure Fan Speed Control
Microprocessor Controlled EC (Electronically Commutated) Fans
Compressor
Screw - Twin
Quantity
1 + 1
1 + 1
1 + 1
1 + 1
1 + 1
Oil Charge Volume (Total)
l
22 + 22
19 + 22
19 + 19
19 + 19
19 + 19
Oil Type
Ester Oil
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve (EEV)
Refrigerant Pre Charged
R134a
Charge (Total)
kg
125 + 125
130 + 125
130 + 130
130 + 130
130 + 130
Connections
Grooved type Coupling & Pipe Assembly
Water Inlet / Outlet
DN200 PN16
DN200 PN16
DN200 PN16
DN200 PN16
DN200 PN16
Water Drain / Bleed
in
1/2
1/2
1/2
1/2
1/2
Water System
Min. System Water Volume
(5)
l
1850
1947
2044
2139
2234
Max. System Operating Pressure
bar
10
10
10
10
10
OPTIONAL EXTRAS
Water Pump - ac Motor
(1)
In Line Pump - Fixed Speed Motor
Single Head or Run/Standby
Nom External Head Single - Standard
kPa
86
84
81
79
76
Nom External Head Single - Larger
kPa
123
121
119
116
179
Water Pump - Inverter Driven Motor
In Line Pump - Variable Speed Motor
Single Head or Run/Standby
Nom External Head Single - Standard
kPa
140
137
135
90
87
Nom External Head Single - Larger
kPa
140
137
135
177
175
Overall Dimensions with Pump
- H x W x L
(6)
mm
2600 x 2570 x
8500
2600 x 2570 x
8500
2600 x 2570 x
8500
2600 x 2570 x
8500
2600 x 2570 x
8500
(1)
Based on 12/7°C water temperature and 35°C ambient.
(2)
EER
=
Output kW
Input kW
Where:
Output kW
= Chilled Water Cooling duty.
Input kW
= Compressor + Fan input power.
(3)
ESEER, for further details, refer to
(4)
Based on standard unit, for units fitted with options, please contact Airedale. Machine weight includes refrigerant charge; operating weight includes
refrigerant charge and water volume.
(5)
For minimum system volume calculations, refer to
Minimum system water volume calculations
(6)
-8, -10 & -12 Fan models; pump mounted externally, refer to
, on page 56 for details.