PUMP PACKAGES (OPTIONAL EXTRAS)

CAUTION

Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty.

Use the formula below and the graphs provided to calculate the External Head Available:

Example

Model Ref.

= OPC800HE+D14

Ambient:

= 35°C

Fluid

= 100% Water

Inlet Fluid Temp.

= 7°C

Outlet Fluid Temp.

= 12°C (5°C

T)

Pump Selection

= Single Standard Head - Standard ac Motor - Fixed Speed Option

Fluid Flow l/s

= 40.0 l/s

EHA (kPa) =

External Head Available

EHA (kPa) =

Total Pump Head Available

-

Unit Waterside Pressure Drop

EHA (kPa) =

123 - 33

EHA (kPa) =

90 kPa