Minimum system water volume calculations, Chillers optichill, Design features & information – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 21
Chillers
OPTICHILL
™
Chillers
21
Technical Manual : 6530166 V1.6.0 02_2013
Design Features & Information
SPECIFIC HEAT CAPACITY (SHC)
% Ethylene Glycol Concentration
0%
10%
20%
30%
40%
Specific Heat Capacity (kJ/kgK)
(1)
4.190
4.115
3.901
3.686
3.474
% Propylene Glycol Concentration
0%
10%
20%
30%
40%
Specific Heat Capacity (kJ/kgK)
(1)
4.190
4.139
4.033
3.903
3.749
(1)
Data quoted for water/glycol solutions at a nominal temperature of 10°C.
CAUTION
Only use the SHC data when calculating fluid VOLUME. USE figure for 0% concentration
(100% water) when applying Glycol Correction Factors, refer to
MINIMUM SYSTEM WATER VOLUME CALCULATIONS
METHOD 1
(Preferred Method)
Where the system permanent heat load is known, the minimum water volume in litres V
min
is:
V
min
=
Water Flow Rate (litres/min)
x
Minimum Compressor Run Time (min)
x
Chiller Loading Factor
Chiller Loading Factor
=
Minimum Turndown (kW) x 1.2
Permanent Heat Load
Minimum Turndown
=
20%
Example:
600kW Chiller at 35°C Ambient, 7/12°C Water, Model OPC600HED10 with a
permanent load of 360kW
Permanent Heat Load
= 360kW
Minimum Turndown
= 20%
V
min =
605.1 x 60
x 5 x
121
x 1.2 = 3495 Litres
4.19 x 5
360
METHOD 2
Where the system permanent heat load is unknown:
V
min
=
Water Flow Rate (litres/hour)
x
Minimum Turndown
x
1.2
x
Minimum Compressor Run Time (Hours)
Minimum Turndown
=
20%
Example:
600kW Chiller at 35°C Ambient, 7/12°C Water, Model OPC600HED10
Minimum Turndown
= 0.20 (20%)
V
min =
605.1 x 3600
0.20 x 1.2 x
5
= 2079 Litres
4.19 x 5
60