Minimum system water volume calculations, Chillers optichill, Design features & information – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 21

Advertising
background image

Chillers

OPTICHILL

Chillers

21

Technical Manual : 6530166 V1.6.0 02_2013

Design Features & Information

SPECIFIC HEAT CAPACITY (SHC)

% Ethylene Glycol Concentration

0%

10%

20%

30%

40%

Specific Heat Capacity (kJ/kgK)

(1)

4.190

4.115

3.901

3.686

3.474

% Propylene Glycol Concentration

0%

10%

20%

30%

40%

Specific Heat Capacity (kJ/kgK)

(1)

4.190

4.139

4.033

3.903

3.749

(1)

Data quoted for water/glycol solutions at a nominal temperature of 10°C.

CAUTION

Only use the SHC data when calculating fluid VOLUME. USE figure for 0% concentration
(100% water) when applying Glycol Correction Factors, refer to

Glycol data

, on page 32.

MINIMUM SYSTEM WATER VOLUME CALCULATIONS

METHOD 1

(Preferred Method)

Where the system permanent heat load is known, the minimum water volume in litres V

min

is:

V

min

=

Water Flow Rate (litres/min)

x

Minimum Compressor Run Time (min)

x

Chiller Loading Factor

Chiller Loading Factor

=

Minimum Turndown (kW) x 1.2

Permanent Heat Load

Minimum Turndown

=

20%

Example:

600kW Chiller at 35°C Ambient, 7/12°C Water, Model OPC600HED10 with a
permanent load of 360kW

Permanent Heat Load

= 360kW

Minimum Turndown

= 20%

V

min =

605.1 x 60

x 5 x

121

x 1.2 = 3495 Litres

4.19 x 5

360

METHOD 2

Where the system permanent heat load is unknown:

V

min

=

Water Flow Rate (litres/hour)

x

Minimum Turndown

x

1.2

x

Minimum Compressor Run Time (Hours)

Minimum Turndown

=

20%

Example:

600kW Chiller at 35°C Ambient, 7/12°C Water, Model OPC600HED10

Minimum Turndown

= 0.20 (20%)

V

min =

605.1 x 3600

0.20 x 1.2 x

5

= 2079 Litres

4.19 x 5

60