Positioning, Optichill ™ chillers, Installation data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 64

Advertising
background image

OPTICHILL

Chillers

64

Chillers

Technical Manual : 6530166 V1.6.0 02_2013

Installation Data

POSITIONING

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly

Levelling should be to +/- 5mm

Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections

Observe airflow and maintenance clearances

Pipework and electrical connections are readily accessible

Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity

Within a side enclosed installation, the fan MUST be higher than the
enclosing structure

Increase airflow and maintenance clearances for side-enclosed or multiple
unit applications

Ensure there are no obstructions directly above the fans

Allow free space above the fans to prevent air recirculation

CAUTION

Prior to connecting services, ensure that the equipment is installed and
completely level.

AIRFLOW &
MAINTENANCE
CLEARANCES

1300mm / (2600mm)

(1)

(1)

(1)

Application

Distance from Overall Base Dimension

Single unit

1300mm

Side-enclosed or multiple units

2600mm