Mechanical data - high efficiency plus, Optichill ™ chillers, General specification – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 44: Chillers, Standard chiller - d

Advertising
background image

OPTICHILL

Chillers

44

Chillers

Technical Manual : 6530166 V1.6.0 02_2013

General Specification

MECHANICAL DATA - HIGH EFFICIENCY PLUS

Standard Chiller - D

OPC500HE+D8 OPC525HE+D10 OPC550HE+D10 OPC600HE+D10 OPC650HE+D10

Capacity

Nom Output - Cooling Only

(1)

kW

531.1

572.5

601.5

629.6

668.4

Nom Input - Cooling Only

(1)

kW

183.3

188.1

201.0

210.5

221.2

EER

(2)

2.90

3.04

2.99

2.99

3.02

ESEER

(3)

3.83

3.82

3.70

3.74

3.82

ECA Energy Technology listed

Capacity Steps

%

0, 20, 40, 50, 60, 70, 80, 90, 100

Dimensions - H x W x L

mm

2600 x 2200 x

4675

2600 x 2200 x

5675

2600 x 2200 x

5675

2600 x 2200 x

5675

2600 x 2200 x

5675

Weight - Machine

(4)

kg

5590

6100

6130

6140

6310

Weight - Operating

(4)

kg

6010

6500

6510

6550

6830

Construction - Material / Colour

Base: Plain Galvanised Steel

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)

Evaporator

Shell & Tube

Insulation

Class O / UV Stable

Water Volume

l

383.7

383.7

383.7

383.7

504.4

Total Max. Water Flow

l/s

55.2

55.2

55.2

55.2

73.6

Condenser

Copper Tube / Aluminium Fins

Face Area (Total)

20.6

25.8

25.8

25.8

25.8

Nominal Airflow

m³/s

45.6

57.0

57.0

57.0

57.0

Condenser Fan & Motor

Axial - Sickle Bladed Fan

Quantity

8

10

10

10

10

Diameter

mm

800

800

800

800

800

Speed Setting

rpm

900

900

900

900

900

Head Pressure Fan Speed Control

Microprocessor Controlled EC (Electronically Commutated) Fans

Compressor

Screw - Twin

Quantity

1 + 1

1 + 1

1 + 1

1 + 1

1 + 1

Oil Charge Volume (Total)

l

22 + 22

19 + 22

19 + 19

19 + 19

19 + 19

Oil Type

Ester Oil

Refrigeration

Dual Circuit

Refrigerant Control

Electronic Expansion Valve (EEV)

Refrigerant Pre Charged

R134a

Charge (Total)

kg

90 + 90

115 + 105

115 + 115

115 + 115

120 + 120

Connections

Grooved type Coupling & Pipe Assembly

Water Inlet / Outlet

DN200 PN16

DN200 PN16

DN200 PN16

DN200 PN16

DN200 PN16

Water Drain / Bleed

in

1/2

1/2

1/2

1/2

1/2

Water System

Min. System Water Volume

(5)

l

1825

1967

2067

2164

2297

Max. System Operating Pressure

bar

10

10

10

10

10

OPTIONAL EXTRAS

Water Pump - ac Motor

(1)

In Line Pump - Fixed Speed Motor

Single Head or Run/Standby

Nom External Head Single - Standard

kPa

87

83

81

78

89

Nom External Head Single - Larger

kPa

124

121

118

116

192

Water Pump - Inverter Driven Motor

In Line Pump - Variable Speed Motor

Single Head or Run/Standby

Nom External Head Single - Standard

kPa

140

137

135

89

100

Nom External Head Single - Larger

kPa

140

137

135

177

187

Overall Dimensions with Pump
- H x W x L

(6)

mm

2600 x 2570 x

6075

2600 x 2570 x

7075

2600 x 2570 x

7075

2600 x 2570 x

7075

2600 x 2570 x

7075

(1)

Based on 12/7°C water temperature and 35°C ambient.

(2)

EER

=

Output kW

Input kW

Where:

Output kW

= Chilled Water Cooling duty.

Input kW

= Compressor + Fan input power.

(3)

ESEER, for further details, refer to

ESEER calculations

, on page 27.

(4)

Based on standard unit, for units fitted with options, please contact Airedale. Machine weight includes refrigerant charge; operating weight includes
refrigerant charge and water volume.

(5)

For minimum system volume calculations, refer to

Minimum system water volume calculations

, on page 21.

(6)

-8, -10 & -12 Fan models; pump mounted externally, refer to

Dimensional Data

, on page 56 for details.