Design Features & Information

MINIMUM SYSTEM WATER VOLUME CALCULATIONS

METHOD 1

Where the system permanent heat load is known:

Vm =

Water Flow Rate (litres/minute) x Minimum Compressor Run Time
(mins) x Chiller Loading Factor

Where

Vm is the minimum water volume in litres
Minimum Compressor Run Time is 2 minutes

Chiller Loading Factor =

Minimum Turndown (kW) x 1.2

Permanent Heat Load

The Chiller Loading Factor limits:
Max

1.00

Min

0.25

Example 250 kW Chiller, 7/12°C Water, Model UCC250DQ-8/2 with a permanent load of 95 kW

Vm =

250 x 60

x 2 x

60 x 1.2

= 1085 Litres

4.19 x 5

95

METHOD 2

Where the system permanent heat load is unknown:

Vm =

Water Flow Rate (litres/hour) x Minimum Turndown Ratio x 1.2

Maximum Compressor Starts per Hour

Where

Minimum Turndown Ratio = Minimum Stage Capacity (kW)

Chiller Full Capacity (kW)

Example 250 kW Chiller, 7/12°C Water, Model UCC250DQ-8/2 permanent load unknown

Vm =

250 x 3600

x

60

x 1.2

x

1

= 1031 Litres

4.19 x 5

250

12

Method 1 is always preferred.