Minimum system water volume calculations, Ultima compact chillers, Design features & information – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 10
ULTIMA COMPACT
Chillers
10
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Design Features & Information
MINIMUM SYSTEM WATER VOLUME CALCULATIONS
METHOD 1
Where the system permanent heat load is known:
Vm =
Water Flow Rate (litres/minute) x Minimum Compressor Run Time
(mins) x Chiller Loading Factor
Where
Vm is the minimum water volume in litres
Minimum Compressor Run Time is 2 minutes
Chiller Loading Factor =
Minimum Turndown (kW) x 1.2
Permanent Heat Load
The Chiller Loading Factor limits:
Max
1.00
Min
0.25
Example 250 kW Chiller, 7/12°C Water, Model UCC250DQ-8/2 with a permanent load of 95 kW
Vm =
250 x 60
x 2 x
60 x 1.2
= 1085 Litres
4.19 x 5
95
METHOD 2
Where the system permanent heat load is unknown:
Vm =
Water Flow Rate (litres/hour) x Minimum Turndown Ratio x 1.2
Maximum Compressor Starts per Hour
Where
Minimum Turndown Ratio = Minimum Stage Capacity (kW)
Chiller Full Capacity (kW)
Example 250 kW Chiller, 7/12°C Water, Model UCC250DQ-8/2 permanent load unknown
Vm =
250 x 3600
x
60
x 1.2
x
1
= 1031 Litres
4.19 x 5
250
12
Method 1 is always preferred.