Waterside pressure drops, Ultima compact chillers, Performance data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 18

Advertising
background image

ULTIMA COMPACT

Chillers

18

Chillers

Technical Manual : Part No 6259543 TM E_1.3.0 04/2013

Performance Data

WATERSIDE PRESSURE DROPS

(1)

CAUTION

Constant water flow MUST be maintained. Variable water volume is
NOT recommended and may invalidate warranty.

Use the formula below to calculate the External Head Available:

Total Pump Head Available

-

Chiller Pressure Drop

=

External Head Available

Example: UCC200D-6/2 9.54 l/s, standard single pump:

145 kPa

-

42 kPa

=

103 kPa

UCC30 - UCC80

(Except UCC75)

CH

IL

LER PRESSU

RE DR

O

P

(k

Pa

)

(2

)

0

10

20

30

40

50

60

70

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

UCC30

UCC40

UCC50

UCC60

UCC70

UCC80

WATERFLOW (l/s)

UCC75 - UCC150

(Except UCC80)

CH

IL

LER PRESSU

RE DR

O

P

(k

Pa

)

(2

)

0

25

50

75

100

125

0

2

4

6

8

10

12

14

UCC75

UCC100

UCC110

UCC125/130

UCC150

WATERFLOW (l/s)

(1)

For glycol solutions, please refer to

Glycol Data

.

(2)

Chiller pressure drop refers to standard unit without optional pumps and/or pipework.

Advertising
This manual is related to the following products: