Ultima compact chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 32: Electrical data

Advertising
background image

ULTIMA COMPACT

Chillers

32

Chillers

Technical Manual : Part No 6259543 TM E_1.3.0 04/2013

General Specification

ELECTRICAL DATA

UCC75D-2/1

UCC100D-2/1

UCC110D-4/2

UCC125D-3/1

UCC130D-4/2

UCC150D-3/1

Unit Data

Nominal Run Amps

(1) A

50

62

69

79

84

93

Maximum Start Amps

(2) A

140

167

175

217

222

246

Permanent Supply

VAC

230 V 1 PH 50 Hz

Mains Supply

VAC

400 V 3 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

16

Rec Mains Fuse Size

A

63

80

100

125

125

125

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

70 (Direct to

MCCB)

70 (Direct to

MCCB)

Direct to Bus Bar

70 (Direct to

MCCB)

Direct to Bus Bar

70 (Direct to

MCCB)

Control Circuit

VAC

24V/230V AC

Evaporator

Pad Heater Rating

W

40

40

80

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

500

Condenser Fan - Per Fan

Quantity

2

2

4

3

4

3

Full Load Amps

A

1.75

1.75

2.70

1.75

2.70

1.75

Locked Rotor Amps

A

6.20

6.20

7.00

6.20

7.00

6.20

Motor Rating

kW

0.98

0.98

1.75

0.98

1.75

0.98

Compressor - Per Compressor

Quantity

4

4

4

2 + 2

2 + 2

4

Motor Rating

kW

6.2

8.1

8.1

8.1 / 11.7

8.1 / 11.7

11.7

Nominal Run Amps

(1) A

11.7

14.6

14.6

14.6 / 22.0

14.6 / 22.0

22.0

Sump Heater Rating

W

65.0

65.0

65.0

65.0 / 75.0

65.0 / 75.0

75.0

Start Amps

(2)

98.0

120.0

120.0

120.0/ 175.0

120.0/ 175.0

175.0

Type Of Start

Direct on line

QUIET DQ

UCC75DQ-2/1

UCC100DQ-3/1

UCC110DQ-4/2

UCC125DQ-3/1

UCC130DQ-4/2

UCC150DQ-4/1

All data as above except:

Condenser Fan - Per Fan

Quantity

2

3

4

3

4

4

Full Load Amps

A

1.15

1.15

1.25

1.15

1.25

1.15

Locked Rotor Amps

A

2.10

2.10

4.50

2.10

4.50

2.10

Motor Rating

kW

0.68

0.68

0.69

0.68

0.69

0.68

SUPER QUIET DSQ

UCC75DSQ-2/1

UCC100DSQ-3/1

UCC110DSQ-4/2

UCC125DSQ-4/1

UCC130DSQ-6/2

UCC150DSQ-4/1

All data as above except:

Condenser Fan - Per Fan

Quantity

2

3

4

4

6

4

Full Load Amps

A

0.83

0.83

0.78

0.83

0.78

0.83

Locked Rotor Amps

A

1.50

1.50

1.50

1.50

1.50

1.50

Motor Rating

kW

0.32

0.32

0.48

0.32

0.48

0.32

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1) A

48

56

63

71

77

85

Maximum Start Amps

(2) A

140

167

175

217

222

246

Recommended Mains Fuse

A

63

80

100

125

125

125

Compressor Nominal Run Amps
- Per Compressor

A

4 x 11

4 x 13

4 x 13

2 x 20 / 2 x 13

2 x 20 / 2 x 13

4 x 20

Electronic Soft-start

Nominal Run Amps

(1) A

50

62

69

79

84

93

Maximum Start Amps

(2) A

97

119

132

147

152

176

Recommended Mains Fuse

A

63

80

100

125

125

125

Single Head Pump (or Run/Standby)

Unit Nominal Run Amps

(1) A

55

67

75

83

90

98

Recommended Mains Fuse

A

80

100

100

125

125

160

Motor Rating

kW

2.2

2.2

3.0

2.2

3.0

2.2

Full Load Amps

A

4.8

4.8

6.1

4.8

6.1

4.8

Larger Single Head Pump (or Run/Standby)

Unit Nominal Run Amps

(1) A

57

69

77

85

92

100

Recommended Mains Fuse

A

80

100

100

125

125

160

Motor Rating

kW

3.0

3.0

4.0

3.0

4.0

3.0

Full Load Amps

A

6.8

6.8

7.7

6.8

7.7

6.8

Twin Head Pump

Unit Nominal Run Amps

(1) A

56

65

75

85

90

99

Recommended Mains Fuse

A

80

100

100

125

125

160

Motor Rating

kW

3.0

3.0

3.0

3.0

3.0

3.0

Full Load Amps

A

6.1

6.1

6.1

6.1

6.1

6.1

Larger Twin Head Pump

Unit Nominal Run Amps

(1) A

58

70

77

86

92

101

Recommended Mains Fuse

A

80

100

100

125

125

160

Motor Rating

kW

4.0

4.0

4.0

4.0

4.0

4.0

Full Load Amps

A

7.7

7.7

7.7

7.7

7.7

7.7

(1)

Based at 12/7°C water and 30°C ambient

(2)

Starting amps refers to the direct on line connections.