Ultima compact chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 32: Electrical data
ULTIMA COMPACT
Chillers
32
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
General Specification
ELECTRICAL DATA
UCC75D-2/1
UCC100D-2/1
UCC110D-4/2
UCC125D-3/1
UCC130D-4/2
UCC150D-3/1
Unit Data
Nominal Run Amps
(1) A
50
62
69
79
84
93
Maximum Start Amps
(2) A
140
167
175
217
222
246
Permanent Supply
VAC
230 V 1 PH 50 Hz
Mains Supply
VAC
400 V 3 PH 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
16
Rec Mains Fuse Size
A
63
80
100
125
125
125
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
70 (Direct to
MCCB)
70 (Direct to
MCCB)
Direct to Bus Bar
70 (Direct to
MCCB)
Direct to Bus Bar
70 (Direct to
MCCB)
Control Circuit
VAC
24V/230V AC
Evaporator
Pad Heater Rating
W
40
40
80
80
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
500
Condenser Fan - Per Fan
Quantity
2
2
4
3
4
3
Full Load Amps
A
1.75
1.75
2.70
1.75
2.70
1.75
Locked Rotor Amps
A
6.20
6.20
7.00
6.20
7.00
6.20
Motor Rating
kW
0.98
0.98
1.75
0.98
1.75
0.98
Compressor - Per Compressor
Quantity
4
4
4
2 + 2
2 + 2
4
Motor Rating
kW
6.2
8.1
8.1
8.1 / 11.7
8.1 / 11.7
11.7
Nominal Run Amps
(1) A
11.7
14.6
14.6
14.6 / 22.0
14.6 / 22.0
22.0
Sump Heater Rating
W
65.0
65.0
65.0
65.0 / 75.0
65.0 / 75.0
75.0
Start Amps
(2)
98.0
120.0
120.0
120.0/ 175.0
120.0/ 175.0
175.0
Type Of Start
Direct on line
QUIET DQ
UCC75DQ-2/1
UCC100DQ-3/1
UCC110DQ-4/2
UCC125DQ-3/1
UCC130DQ-4/2
UCC150DQ-4/1
All data as above except:
Condenser Fan - Per Fan
Quantity
2
3
4
3
4
4
Full Load Amps
A
1.15
1.15
1.25
1.15
1.25
1.15
Locked Rotor Amps
A
2.10
2.10
4.50
2.10
4.50
2.10
Motor Rating
kW
0.68
0.68
0.69
0.68
0.69
0.68
SUPER QUIET DSQ
UCC75DSQ-2/1
UCC100DSQ-3/1
UCC110DSQ-4/2
UCC125DSQ-4/1
UCC130DSQ-6/2
UCC150DSQ-4/1
All data as above except:
Condenser Fan - Per Fan
Quantity
2
3
4
4
6
4
Full Load Amps
A
0.83
0.83
0.78
0.83
0.78
0.83
Locked Rotor Amps
A
1.50
1.50
1.50
1.50
1.50
1.50
Motor Rating
kW
0.32
0.32
0.48
0.32
0.48
0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1) A
48
56
63
71
77
85
Maximum Start Amps
(2) A
140
167
175
217
222
246
Recommended Mains Fuse
A
63
80
100
125
125
125
Compressor Nominal Run Amps
- Per Compressor
A
4 x 11
4 x 13
4 x 13
2 x 20 / 2 x 13
2 x 20 / 2 x 13
4 x 20
Electronic Soft-start
Nominal Run Amps
(1) A
50
62
69
79
84
93
Maximum Start Amps
(2) A
97
119
132
147
152
176
Recommended Mains Fuse
A
63
80
100
125
125
125
Single Head Pump (or Run/Standby)
Unit Nominal Run Amps
(1) A
55
67
75
83
90
98
Recommended Mains Fuse
A
80
100
100
125
125
160
Motor Rating
kW
2.2
2.2
3.0
2.2
3.0
2.2
Full Load Amps
A
4.8
4.8
6.1
4.8
6.1
4.8
Larger Single Head Pump (or Run/Standby)
Unit Nominal Run Amps
(1) A
57
69
77
85
92
100
Recommended Mains Fuse
A
80
100
100
125
125
160
Motor Rating
kW
3.0
3.0
4.0
3.0
4.0
3.0
Full Load Amps
A
6.8
6.8
7.7
6.8
7.7
6.8
Twin Head Pump
Unit Nominal Run Amps
(1) A
56
65
75
85
90
99
Recommended Mains Fuse
A
80
100
100
125
125
160
Motor Rating
kW
3.0
3.0
3.0
3.0
3.0
3.0
Full Load Amps
A
6.1
6.1
6.1
6.1
6.1
6.1
Larger Twin Head Pump
Unit Nominal Run Amps
(1) A
58
70
77
86
92
101
Recommended Mains Fuse
A
80
100
100
125
125
160
Motor Rating
kW
4.0
4.0
4.0
4.0
4.0
4.0
Full Load Amps
A
7.7
7.7
7.7
7.7
7.7
7.7
(1)
Based at 12/7°C water and 30°C ambient
(2)
Starting amps refers to the direct on line connections.