Chillers
ULTIMA COMPACT
Chillers
19
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Performance Data
WATERSIDE PRESSURE DROPS
(1)
CAUTION
Constant water flow MUST be maintained. Variable water volume is
NOT recommended and may invalidate warranty.
UCC160 - UCC250
CH
IL
LER PRESSU
RE DR
O
P
(k
Pa
)
(2
)
0
25
50
75
100
125
2
4
6
8
10
12
14
16
18
20
UCC160
UCC250
UCC225
UCC200
UCC180
WATERFLOW (l/s)
UCC275 - UCC450
(Except UCC250)
CH
IL
LER PRESSU
RE DR
O
P
(k
Pa
)
(2
)
0
20
40
60
80
100
120
0
5
10
15
20
25
30
35
UCC275
UCC300
UCC330
UCC360
UCC400
UCC450
WATERFLOW (l/s)
(1)
For glycol solutions, please refer to
(2)
Chiller pressure drop refers to standard unit without optional pumps and/or pipework.
Advertising