Ultima compact chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 30: Mechanical data
ULTIMA COMPACT
Chillers
30
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
General Specification
MECHANICAL DATA
UCC300D-8/2
UCC330D-10/2
UCC360D-10/2
UCC400D-12/2
UCC450D-12/2
Duty - Cooling
Cooling Only
(1) kW
319.7
358.5
392.2
439.1
486.5
Nominal Input
(1) kW
103.5
104.2
115.5
127.6
143.7
EER
(2)
3.09
3.44
3.40
3.44
3.39
Capacity Steps
%
0-25-50-75-100
0-19-33-52-67-85-100
0-17-33-50-67-83-100
0-18-33-51-67-85-100
0-17-33-50-67-83-100
Dimensions - H x L x W
mm
2180 x 4720 x 2200
2180 x 5570 x 2200
2180 x 5570 x 2200
2180 x 6420 x 2200
2180 x 6420 x 2200
Weight - Machine
(3) kg
2760
2950
3170
3560
3680
Weight - Operating
(3) kg
2820
3020
3240
3640
3770
Construction - Material / Colour
Plain Galvanised Steel Base with Galvanised Sheet Steel, Epoxy Baked Powder Paint Superstructure- Light Grey (RAL 7035)
Evaporator Type/Insulation
Brazed Plate / Class 1
Water Volume (Total Internal)
l
55.5
65.8
70.3
82.4
89.6
Total Max. Water Flow
l/s
21.5
24.4
27.1
30.3
33.0
Condenser
Copper Tube/ Aluminium Fins - Air Cooled
Face Area (Total)
m²
11.0
13.8
13.8
16.5
16.5
Nominal Airflow
m³/s
24.8
31.0
31.0
37.2
37.2
Fan & Motor
Sickle Bladed Fan
Quantity
8
10
10
12
12
Diameter
mm
710
710
710
710
710
Maximum Speed
rpm
1000
1000
1000
1000
1000
Compressor
Tandem Scroll
Trio Scroll
Quantity
4
6
6
6
6
Oil Charge Volume (Total)
l
4 x 8.0
6 x 8.0
6 x 8.0
6 x 8.0
6 x 8.0
Oil Type
Polyol Ester
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve (EEV)
Refrigerant Precharged
R407C
R407C
R407C
R407C
R407C
Charge (Total)
kg
42 + 42
43 + 39
53 + 53
65 + 60
63 + 63
Connections
Water Inlet / Outlet
(4)
DN 100
DN 100
DN 100
DN 100
DN 100
Water Drain/Bleed
in
1/2
1/2
1/2
1/2
1/2
Water System
Min. System Water Volume
(5) l
897
1130
1122
1322
1348
Max. System Press
Bar
10
10
10
10
10
QUIET DQ
UCC300DQ-10/2
UCC330DQ-10/2
UCC360DQ-12/2
UCC400DQ-12/2
UCC450DQ-14/2
All data as D Model except:
Cooling Duty
(1) kW
318.5
355.7
392.1
432.5
485.2
Nominal Input
(1) kW
103.8
105.9
115.5
131.5
144.4
EER
(2)
3.07
3.36
3.39
3.29
3.36
Dimensions, H x L x W
mm
2180 x 5570 x 2200
2180 x 5570 x 2200
2180 x 6420 x 2200
2180 x 6420 x 2200
2180 x 7270 x 2200
Weight - Machine
(3) kg
2930
3150
3330
3610
3990
Weight - Operating
(3) kg
2990
3220
3410
3690
4090
Evaporator - Water Volume (Total
Internal)
l
62.2
65.8
77.0
82.4
96.2
Condenser Face Area (Total)
m
2
13.8
13.8
16.5
16.5
19.3
Nominal Airflow
m³/s
24.5
24.5
29.4
29.4
34.3
Condenser Fans, number
10
10
12
12
14
Maximum Fan Speed
rpm
750
750
750
750
750
Refrigerant Charge (Total)
kg
40 + 40
54 + 49
49 + 49
65 + 60
72 + 72
Refrigeration Control
Electronic Expansion Valve
SUPER QUIET DSQ
UCC300DSQ-12/2
UCC330DSQ-14/2
UCC360DSQ-14/2
UCC400DSQ-16/2
UCC450DSQ-16/2
All data as D Model except:
Cooling Duty
(1) kW
315.3
352.7
387.7
430.7
470.7
Nominal Input
(1) kW
104.6
107.7
118.3
132.5
157.1
EER
(2)
3.01
3.28
3.28
3.25
3.10
Dimensions, H x L x W
mm
2180 x 6420 x 2200
2180 x 7270 x 2200
2180 x 7270 x 2200
2180 x 8120 x 2200
2180 x 8120 x 2200
Weight - Machine
(3) kg
3240
3550
3800
4190
4310
Weight - Operating
(3) kg
3310
3630
3880
4290
4410
Condenser Face Area (Total)
m
2
16.5
19.3
19.3
22.0
22.0
Nominal Airflow
m³/s
20.4
23.8
23.8
27.2
27.2
Condenser Fans, number
12
14
14
16
16
Maximum Fan Speed
rpm
570
570
570
570
570
Refrigerant Charge (Total)
kg
46 + 46
56 + 51
70 + 70
82 + 76
80 + 80
Refrigeration Control
Electronic Expansion Valve
OPTIONAL EXTRAS - ALL MODELS
Water Pump
(1)
In Line Pump
Nom External Head Std Single / R&S
kPa
98
137
135
128
125
Nom External Head Larger
Single/R&S
kPa
162
158
156
151
181
Nom External Head Standard Twin
kPa
127
119
115
105
127
Nom External Head Larger Twin
kPa
160
156
154
148
175
Expansion Tank
(6)
Water Capacity
l
50
50
50
50
50
Buffer Tank
(7)
Max. Water Capacity - D
l
420
420
420
420
420
Max. Water Capacity - SQ/DQ
l
420
420
420
420
420
Max. Water Capacity - SSQ/DSQ
l
420
420
420
420
420
Pressurisation Unit
Water Inlet Connection
in
1/2
1/2
1/2
1/2
1/2
(1)
Nominal Cooling Duties based on 12/7°C water temperature and 30°C ambient, where output is the chilled water duty and input i s the compressor input power.
(2)
EER is the Cooling duty
compressor input power.
(3)
Based on standard unit, for units fitted with pump, tank and expansion vessel options, please contact Airedale.
(4)
Flanged to PN16.
(5)
For minimum system volume, refer to
Design Features & Information - Minimum System Water Volume Calculations
(6)
Expansion vessel may require reselecting for glycol and system volume, please refer to Airedale
(7)
8 Fan units only: Maximum Water Capacity becomes 250 litres when the pump option is also selected.