Ultima compact chillers, Design features & information – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 12
ULTIMA COMPACT
Chillers
12
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Design Features & Information
FEATURES
Temperature
The microprocessor maintains the set supply Chilled Water temperature by sensing the
return and supply water temperatures and manages the compressor loading.
The microprocessor also monitors and displays the following measured parameters:
Supply Water Temperature
Return Water Temperature
Suction Pressure of each circuit
Liquid Pressure of each circuit
Suction Temperature at each circuit (when the EEV option is fitted)
Superheat for each circuit (when the EEV option is fitted)
Alarms
The following conditions will be detected, triggering a visual display:
Common for both circuits (Dual Circuit units):
Low Supply Temperature
Emergency Stop
Water Flow
Pump(s) status
Pump(s) remote start
Individual for each circuit:
Individual alarms will isolate the affected circuit only.
Compressor Trip
Low Suction Pressure for each circuit
High Liquid Pressure for each circuit
Volt Free Contact Alarm Indication
Low Pressure Switch
Compressor Overload
High Compressor Discharge Temperature
Networking
A Local Area Network (
) can be used to connect a number of chiller controllers to
offer intercommunication and sequence control. There is also the facility to allow the
connection of either a computer or modem for local or remote monitoring.
For further
details, please contact Airedale.