Operating limits, Glycol data, Chillers ultima compact – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 17: Performance data
Chillers
ULTIMA COMPACT
Chillers
17
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Performance Data
OPERATING LIMITS
(For 100% Water)
Standard Unit
Minimum Ambient Air DB °C
-5°C
Maximum Ambient Air DB °C
Refer to
Performance Data - Capacity Data
Minimum Leaving Water Temperature °C
+6°C
Maximum Return Water Temperature °C
+20°C
Unit with Electronic Fan Speed HP Control (-20°C)
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
Refer to
Performance Data - Capacity Data
Minimum Leaving Water Temperature °C
+6°C
Maximum Return Water Temperature °C
+20°C
1
Temperatures lower than those stated can be obtained with the addition of glycol.
2
For conditions outside those quoted, please refer to Airedale.
GLYCOL DATA
Glycol is recommended when a supply water temperature of +5°C or below is required or
when static water can be exposed to freezing temperatures.
Ethylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
10% / -4°C
20% / -9°C
30% / -15°C
40% / -23°C
Cooling Duty
Catalogue Data x by:
0.98
0.97
0.95
0.93
Input Power
0.99
0.98
0.96
0.95
Water Flow
0.99
1.02
1.04
1.07
Pressure Drop
1.05
1.20
1.38
1.57
Propylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
10% / -2°C
20% / -6°C
30% / -12°C
40% / -20°C
Cooling Duty
Catalogue Data x by:
0.97
0.95
0.91
0.88
Input Power
0.99
0.98
0.96
0.95
Water Flow
0.98
0.97
0.95
0.95
Pressure Drop
1.08
1.17
1.31
1.45
Example
UCC250D-6/2 operating at 7/12, 30°C Ambient, 20% Ethylene Glycol
Catalogue
Figure Multiplier
Corrected
Figure
Cooling kW
(refer to
Performance Data - Capacity Data
269.2
x 0.97
20%
Ethylene
Glycol =
261.1 kW
Input kW
(refer to
Performance Data - Capacity Data
79.2
x 0.98
77.6 kW
Flow l/s
calculated
(DX (Mechanical Cooling kW)
12.8
x 1.02
13.1 l/s
T x 4.19
Pressure Drop kPa
(refer to
50.0
x 1.20
60.0 kPa