Interconnecting wiring, Ultima compact chillers, Installation data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 46: Chillers, Interconnecting wiring no pumps, Caution, Double circuit
ULTIMA COMPACT
Chillers
46
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
Installation Data
INTERCONNECTING WIRING
No Pumps
Single Circuit
(not including: leak detector,
remote setpoint adjust and
differential pressure switch)
UCC30 - UCC80
(Excluding UCC75)
L1
Mains incoming supply 400V/3PH/50Hz
(N2 only required for Models 30-80Q & 50-70SQ)
L2
L3
N2
E
L4
Separate Permanent Supply 230V/1PH/50Hz
N1
E
2
External Trace Heating Connections
N
240V/500W max
506
(1) Evaporator Remote Pump Interlock 24Vac
522
506
(1) Evaporator Pump Water Flow Switch
504
506
Unit Remote On/Off
505
573
Circuit 1
Volt Free Common Alarm
574
Volt Free Alarm N/O
575
Volt Free Alarm N/C
RX-/Tx-
RX+/Tx+
Network Connections
GND
Double Circuit
UCC30 - UCC450
L1
Mains incoming supply 400V/3PH/50Hz
(N2 only required for Models 30-80DQ & 50-70DSQ)
L2
L3
N2
E
L4
Separate Permanent Supply 230V/1PH/50Hz
N1
E
2
External Trace Heating Connections
N
240V/500W max
502
(1) Evaporator Remote Pump Interlock 24VAC
522
502
(1) Evaporator Pump Water Flow Switch 24VAC
504
502
Unit Remote On/Off 24VAC
505
502
Setback Setpoint Temperature switch
507
573
Circuit 1
Volt Free Common Alarm
574
Volt Free Alarm N/O
575
Volt Free Alarm N/C
576
Circuit 2
Volt Free Common Alarm
Dual Circuit Only
577
Volt Free Alarm N/O
578
Volt Free Alarm N/C
RX-/Tx-
RX+/Tx+
Network Connections
GND
CAUTION
(1) MUST be directly wired to the chiller to validate warranty.