Interconnecting wiring, Ultima compact chillers, Installation data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 46: Chillers, Interconnecting wiring no pumps, Caution, Double circuit

Advertising
background image

ULTIMA COMPACT

Chillers

46

Chillers

Technical Manual : Part No 6259543 TM E_1.3.0 04/2013

Installation Data

INTERCONNECTING WIRING

No Pumps

Single Circuit
(not including: leak detector,
remote setpoint adjust and
differential pressure switch)

UCC30 - UCC80

(Excluding UCC75)

L1

Mains incoming supply 400V/3PH/50Hz
(N2 only required for Models 30-80Q & 50-70SQ)

L2

L3

N2

E

L4

Separate Permanent Supply 230V/1PH/50Hz

N1

E

2

External Trace Heating Connections

N

240V/500W max

506

(1) Evaporator Remote Pump Interlock 24Vac

522

506

(1) Evaporator Pump Water Flow Switch

504

506

Unit Remote On/Off

505

573

Circuit 1

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

RX-/Tx-



RX+/Tx+



Network Connections

GND



Double Circuit

UCC30 - UCC450

L1

Mains incoming supply 400V/3PH/50Hz
(N2 only required for Models 30-80DQ & 50-70DSQ)

L2

L3

N2

E

L4

Separate Permanent Supply 230V/1PH/50Hz

N1

E

2

External Trace Heating Connections

N

240V/500W max

502

(1) Evaporator Remote Pump Interlock 24VAC

522

502

(1) Evaporator Pump Water Flow Switch 24VAC

504

502

Unit Remote On/Off 24VAC

505

502

Setback Setpoint Temperature switch

507

573

Circuit 1

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

576

Circuit 2

Volt Free Common Alarm

Dual Circuit Only

577

Volt Free Alarm N/O

578

Volt Free Alarm N/C

RX-/Tx-



RX+/Tx+



Network Connections

GND



CAUTION

(1) MUST be directly wired to the chiller to validate warranty.