Design Features & Information

CONTROLS

General Description

The

microprocessor controller offers powerful analogue and digital control to

meet a wide range of monitoring and control features including a real time clock and
Industry standard communication port and network connections.

The controller’s inbuilt display is used for viewing the unit operating status and making
adjustments to control parameters by allowing the operator access to a series of
display pages.

Also featured are a visual alarm and the facility to adjust and display control settings by
local operator for information and control.

Display/Keypad

5

3

6

2

1

4

08:44 13/05/02 Mst
Remote 0-10V Input
Signal Voltage 05.6V
Unit ON

7

Esc

Prg

1 UP/DOWN KEYS

To change Adjustable Fields & Scrolls
up & down available Menus

2 ENTER

Selects Menus & Moves Cursor to
Adjustable Fields Green LED

3 ESC

Green LED lit when Operating Page
displayed, Returns to Operating Page
Screen when pressed

4 PROGRAM

Opens the Available Menus

5 ALARM

Red LED Indicates Alarm Present

6 4 ROW LCD DISPLAY
7 CURSOR (FLASHING): Top Left

Position =

“HOME” Indicates adjustable

Fields

FEATURES

Unit Remote ON/OFF

Disables/Enables the chiller remotely.

Compressor Anti Cycle
Control

Automatic via the Microprocessor.

Compressor Load Limit

Limits the condensing pressure by unloading above 24Barg.

Limits the evaporating pressure by unloading at the minimum pressure setpoint, which is,
adjustable depending on system glycol content.

Pump(s) Remote
ON/OFF

Disables/Enables the pump(s) remotely.

Remote Setback
Temperature Setpoint
Switch

A setback setpoint for supply water temperature can be selected to suit summer/winter
conditions or night setback.

Compressor Hours Run

Displays hours run of each compressor.

Pumps Hours Run

Displays hours run of each pump.

Password Protection

The control system integrity can be maintained by restricting access with a password
PIN number.

CAUTION

IMPORTANT: To change the PIN number, please contact Airedale at time of order
with the preferred 4 digit number.