Ultima compact chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 34: Electrical data
ULTIMA COMPACT
Chillers
34
Chillers
Technical Manual : Part No 6259543 TM E_1.3.0 04/2013
General Specification
ELECTRICAL DATA
UCC300D-8/2
UCC330D-10/2
UCC360D-10/2
UCC400D-12/2
UCC450D-12/2
Unit Data
Nominal Run Amps
(1) A
173
198
216
240
260
Maximum Start Amps
(2) A
454
435
453
520
540
Permanent Supply
VAC
230 V 1 PH 50 Hz
Mains Supply
VAC
400 V 3 PH 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
Rec Mains Fuse Size
A
200
250
315
315
355
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Control Circuit
VAC
24V/230V AC
Evaporator
Pad Heater Rating
W
100
100
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
Condenser Fan - Per Fan
Quantity
8
10
10
12
12
Full Load Amps
A
1.75
1.75
1.75
1.75
1.75
Locked Rotor Amps
A
6.20
6.20
6.20
6.20
6.20
Motor Rating
kW
0.98
0.98
0.98
0.98
0.98
Compressor - Per Compressor
Quantity
4
3 + 3
6
3 + 3
6
Motor Rating
kW
22.8
18.2 / 15.0
18.2
22.8 / 18.2
22.8
Nominal Run Amps
(1) A
40.0
33.0 / 27.0
33.0
40.0 / 33.0
40.0
Sump Heater Rating
W
130.0
130.0 / 130.0
130.0
130.0 / 130.0
130.0
Start Amps
(2)
320.0
270.0 / 215.0
270.0
320.0 / 270.0
320.0
Type Of Start
Direct on line
QUIET DQ
UCC300DQ-10/2
UCC330DQ-10/2
UCC360DQ-12/2
UCC400DQ-12/2
UCC450DQ-14/2
All data as above except:
Condenser Fan - Per Fan
Quantity
10
10
12
12
14
Full Load Amps
A
1.15
1.15
1.15
1.15
1.15
Locked Rotor Amps
A
2.10
2.10
2.10
2.10
2.10
Motor Rating
kW
0.70
0.70
0.70
0.70
0.70
SUPER QUIET DSQ
UCC300DSQ-12/2
UCC330DSQ-14/2
UCC360DSQ-14/2
UCC400DSQ-16/2
UCC450DSQ-16/2
All data as above except:
Condenser Fan - Per Fan
Quantity
12
14
14
16
16
Full Load Amps
A
0.83
0.83
0.83
0.83
0.83
Locked Rotor Amps
A
1.50
1.50
1.50
1.50
1.50
Motor Rating
kW
0.32
0.32
0.32
0.32
0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1) A
158
180
198
219
237
Maximum Start Amps
(2) A
442
435
453
520
540
Recommended Mains Fuse
A
200
250
250
250
315
Compressor Nominal Run Amps
- Per Compressor
A
4 x 36
3 x 30 / 3 x 24
6 x 30
3 x 36 / 3 x 30
6 x 36
Electronic Soft-start
Nominal Run Amps
(1) A
173
198
216
240
260
Maximum Start Amps
(2) A
314
327
345
392
412
Recommended Mains Fuse
A
200
250
315
315
355
Single Head Pump (or Run/Standby)
Unit Nominal Run Amps
(1) A
189
210
228
252
272
Recommended Mains Fuse
A
250
250
315
315
355
Motor Rating
kW
5.5
7.5
7.5
7.5
7.5
Full Load Amps
A
11.7
15.2
15.2
15.2
15.2
Larger Single Head Pump (or Run/Standby)
Unit Nominal Run Amps
(1) A
197
220
238
261
282
Recommended Mains Fuse
A
250
315
315
315
355
Motor Rating
kW
11.0
11.0
11.0
11.0
11.0
Full Load Amps
A
21.5
21.5
21.5
21.5
21.5
Twin Head Pump
Unit Nominal Run Amps
(1) A
185
209
227
251
275
Recommended Mains Fuse
A
250
250
315
315
355
Motor Rating
kW
5.5
5.5
5.5
5.5
7.5
Full Load Amps
A
11.7
11.7
11.7
11.7
15.2
Larger Twin Head Pump
Unit Nominal Run Amps
(1) A
198
220
238
262
282
Recommended Mains Fuse
A
250
315
315
315
355
Motor Rating
kW
11.0
11.0
11.0
11.0
11.0
Full Load Amps
A
21.5
21.5
21.5
21.5
21.5
(1)
Based at 12/7°C water and 30°C ambient
(2)
Starting amps refers to the direct on line connections.