General Specification

ELECTRICAL DATA

UCC30SQ-1/1

UCC30DQ-1/1

UCC40SQ-1/1

UCC40DQ-1/1

UCC50SQ-2/1

UCC50DQ-2/1

UCC60SQ-2/1

UCC60DQ-2/1

UCC70SQ-2/1

UCC70DQ-2/1

UCC80SQ-2/1

UCC80DQ-2/1

Unit Data

Nominal Run Amps

(1) A

22

27

35

38

41

51

Maximum Start Amps

(2) A

109

113

141

156

159

204

Permanent Supply

VAC

230 V 1 PH 50 Hz

Mains Supply

VAC

400 V 3 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

16

Rec Mains Fuse Size

A

32

40

50

50

63

80

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Max Mains Incoming Cable Size

mm²

35 (Direct to Isolator)

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

40

40

40

40

40

40

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

500

Condenser Fan - Per Fan

Quantity

1

1

2

2

2

2

Full Load Amps

A

3.0

3.5

3.0

3.0

3.0

3.5

Locked Rotor Amps

A

7.0

7.5

7.0

7.0

7.0

7.5

Motor Rating

kW

0.63

0.78

0.63

0.63

0.63

0.78

Compressor - Per Compressor

Quantity

2

2

2

2

2

2

Motor Rating

kW

4.7

6.2

8.1

9.5 / 8.1

9.5

11.7

Nominal Run Amps

(1) A

9.3

11.7

14.6

17.6 / 14.6

17.6

22.0

Sump Heater Rating

W

70.0

65.0

65.0

65.0 / 75.0

65.0

70.0

Start Amps

(2)

101.0

98.0

120.0

135.0/120.0

135.0

175.0

Type Of Start

Direct on line

SUPER QUIET SQ

UCC30SSQ-1/1
UCC30DSQ-1/1

UCC40SSQ-1/1
UCC40DSQ-1/1

UCC50SSQ-2/1
UCC50DSQ-2/1

UCC60SSQ-2/1
UCC60DSQ-2/1

UCC70SSQ-2/1
UCC70DSQ-2/1

UCC80SSQ-2/1
UCC80DSQ-2/1

All data as above except:

Condenser Fan - Per Fan

Full Load Amps

A

1.15

1.15

3.50

3.50

3.50

1.15

Locked Rotor Amps

A

2.10

2.10

7.50

7.50

7.50

2.10

Motor Rating

kW

0.70

0.70

0.78

0.78

0.78

0.70

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1) A

N/A

N/A

N/A

N/A

N/A

N/A

Maximum Start Amps

(2) A

N/A

N/A

N/A

N/A

N/A

N/A

Recommended Mains Fuse

A

N/A

N/A

N/A

N/A

N/A

N/A

Compressor Nominal Run Amps
- Per Compressor

A

N/A

N/A

N/A

N/A

N/A

N/A

Electronic Soft-start

Nominal Run Amps

(1) A

22

27

35

38

41

51

Maximum Start Amps

(2) A

73

74

93

102

105

112

Recommended Mains Fuse

A

32

40

50

50

63

80

Single Head Pump (or Run/Standby)

Unit Nominal Run Amps

(1) A

24

29

38

41

44

54

Recommended Mains Fuse

A

40

50

63

63

63

80

Motor Rating

kW

0.55

0.55

0.90

0.90

1.10

1.10

Full Load Amps

A

1.9

1.9

2.7

2.7

2.9

2.9

Larger Single Head Pump (or Run/Standby)

Unit Nominal Run Amps

(1) A

24

30

39

42

45

54

Recommended Mains Fuse

A

40

50

63

63

63

80

Motor Rating

kW

0.75

0.90

1.50

1.50

1.50

1.50

Full Load Amps

A

2.3

3.0

4.0

4.0

3.4

3.4

Twin Head Pump

Unit Nominal Run Amps

(1) A

25

30

38

41

44

54

Recommended Mains Fuse

A

40

50

63

63

63

80

Motor Rating

kW

1.5

1.5

1.5

1.5

1.5

1.5

Full Load Amps

A

3.2

3.2

3.2

3.2

3.2

3.2

Larger Twin Head Pump

Unit Nominal Run Amps

(1) A

26

32

40

43

46

56

Recommended Mains Fuse

A

40

50

63

63

63

80

Motor Rating

kW

2.2

2.2

2.2

2.2

2.2

2.2

Full Load Amps

A

4.6

4.6

4.6

4.6

4.6

4.6

(1)

Based at 12/7°C water and 30°C ambient

(2)

Starting amps refers to the direct on line connections.