Chillers ultima compact, Installation data, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 47: Interconnecting wiring, With pumps, Double circuit

Advertising
background image

Chillers

ULTIMA COMPACT

Chillers

47

Technical Manual : Part No 6259543 TM E_1.3.0 04/2013

Installation Data

INTERCONNECTING WIRING

With Pumps

Single Circuit
(not including: leak detector,
remote setpoint adjust and
differential pressure switch)

UCC30 - UCC80

(Excluding UCC75)

L1

Mains incoming supply 400V/3PH/50Hz
(N2 only required for Models 30-80Q & 50-70SQ)

L2

L3

N2

E

L4

Separate Permanent Supply 230V/1PH/50Hz

N1

E

2

External Trace Heating Connections

N

240V/500W max

506

Unit Remote On/Off

505

573

Circuit 1

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

RX-/Tx-



RX+/Tx+



Network Connections

GND



Double Circuit

UCC30 - UCC450

L1

Mains incoming supply 400V/3PH/50Hz
(N2 only required for Models 30-80DQ & 50-70DSQ)

L2

L3

N2

E

L4

Separate Permanent Supply 230V/1PH/50Hz

N1

E

2

External Trace Heating Connections

N

240V/500W max

502

Pump’s Remote On/Off 24VAC

506

502

Unit Remote On/Off 24VAC

505

502

Setback Setpoint Temperature switch

507

573

Circuit 1

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

576

Circuit 2

Volt Free Common Alarm

Dual Circuit Only

577

Volt Free Alarm N/O

578

Volt Free Alarm N/C

RX-/Tx-



RX+/Tx+



Network Connections

GND

