NORD Drivesystems BU0050 User Manual

Page 14

Advertising
background image

NORD USS and Modbus RTU Manual

14

Subject to technical amendments

BU 0050 GB-3111

1.2.2.4

Customer unit Standard I/O

(SK CU1-STD, Option)

The standard I/O of the customer interface(Customer Unit) provides
sufficient control terminals for most applications and it is fully
terminal-compatible with NORDAC vector mc.

.

1 analog differential input, 4 digital inputs and 1 analog output are
available for control of the frequency inverter.

Readiness for operation is shown via the 2 relay contacts and a
mechanical motor brake is activated at the correct time.

The connected frequency inverter can be accessed via the RS485
interface
. In addition to the entire range of control functions,
parameterisation is also possible.

TheNORD CON software can be used to carry out a simple function
test of the serial interface and the parameterisation of the inverter.
For this, an interface converter (e.g. SK IC1-232/485) must be used
between

the

PC

and

the

inverter.

Following

successful

parameterisation, the complete data set can be stored as a file by
means of NORD CON.

Connector

Functions

Maximum cross-section

Parameter

X1.1

Output relay

1,5 mm

2

P434 ... P443

X1.2

Analog signals IN / OUT

1,0 mm

2

P400 ... P419

X1.3

Digital inputs

1,0 mm

2

P420 ... P423

X1.4

Bus signals / power supply

1,0 mm

2

P503 ... P548

74 RS485 -

X

1

.1

X

1

.2

X

1

.3

X

1

.4

11 VREF 10V
12 AGND /0V
13 AIN1 -
14 AIN1 +
17 AOUT1

21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
24 DIG IN 4
42 VO +15V

41 VO +5V
40 GND /0V
73 RS485 +

01 REL1.1

02 REL1.2

03 REL2.1

04 REL2.2























NOTE: All control voltages are based on a common reference potential!

Potentials AGND /0V and GND /0V are internally linked in the device.

The maximum total current 5/15V is 300mA!

Potentialfreier Kontakt oder
Ausgang einer SPS: 7,5...33V

(low = 0...3,5Volt)

Differenzeingang 0...10V

0...20mA

Voltage supply: 5V

RS 485 (USS protocol)

5V supply for ParameterBox,

p-box or motor thermistor

Data cables USS protocol

Digitale Eingänge:

DIG IN 1 = Ein rechts

DIG IN 2 = Ein links

DIG IN 3 = Parametersatz bit 0

DIG IN 4 = Festfrequenz 1

Ausgangsrelais:

max. 2,0A

28V DC /230V AC

U

REF

= 10V / I

max

= 10 mA

Analogausgang SPS: 0...10V
oder Potentiometer: 2...10k

Spannungsversorgung: 15V

Termination resistor for
RS 485 interface (120

)

Zuschaltbarer Bürdenwiderstand für
0/4...20mA Analogeingang (250

)


U/I switching

Analog input,

250

ON = Current,

OFF = Voltage

Termination

resistor
RS 485

120

O
F
F

ON

O
F
F

ON