2.5 Modbus RTU: Function codes

BU 0050 GB-3111

Subject to technical amendments

67

Example 1:

Parameter P613 [0] is written with the value 0x00123456.

Query (Master

Slave)

Response (Slave

Master)

Address

0x08

Address

0x08

Function Code

0x10

Function Code

0x10

Start address High

0x99

Start address High

0x99

Start address Low

0x40

Start address Low

0x40

Number of parameters High

0x00

Number of parameters High

0x00

Number of parameters Low

0x02

Number of parameters Low

0x02

Number of bytes

0x04

CRC High

0x6E

Parameter value 1 High

0x00

CRC Low

0x19

Parameter value 1 Low

0x12

Parameter value 2 High

0x34

Parameter value 2 Low

0x56

CRC High

0x29

CRC Low

0xAE

Example 2:

Parameters P050[1] to P050[3], i.e. setpoint values 1 to 3 are written.

Control word1 = 1000 // SW2 = 2000 // SW3 = 3000.

Query (Master

Slave)

Response (Slave

Master)

Address

0x08

Address

0x08

Function Code

0x10

Function Code

0x10

Start address High

0x0C

Start address High

0x0C

Start address Low

0x81

Start address Low

0x81

Number of parameters High

0x00

Number of parameters High

0x00

Number of parameters Low

0x03

Number of parameters Low

0x03

Number of bytes

0x06

CRC High

0xD3

Parameter value 1 High

0x03

CRC Low

0xE9

Parameter value 1 Low

0xE8

Parameter value 2 High

0x07

Parameter value 2 Low

0xD0

Parameter value 3 High

0x0B

Parameter value 3 Low

0xB8

CRC High

0xF5

CRC Low

0xDF