NORD USS and Modbus RTU Manual

70

Subject to technical amendments

BU 0050 GB-3111

Parameter access

The FI parameters cannot be directly accessed via the functions 03h, 06h or 10h, as many FI parameters have
array elements. Therefore, the addresses for NORD parameters are according to the following model:

Start address

Bit 15

– Bit 6

Bit 5

– Bit 0

Parameter number

Array Index

The lower 5 bits are available for the array elements, so that the maximum array size is 63. The parameter
values are shifted by 6 places.

Examples

P102 Parameter set 1 = 0x1980

P102 Parameter set 2 = 0x1981

P510 Array element 2 = 0x7F81

NOTE

The description of the inverter parameters can be found in the main manual for the frequency
inverter (BU0500). However, parameters related to bus communication can also be found in
Section 1.8 .