NORD Drivesystems BU0050 User Manual

Page 54

Advertising
background image

NORD USS and Modbus RTU Manual

54

Subject to technical amendments

BU 0050 GB-3111

Parameter

Setting value / Description / Note

Comments

P543 (P)

Bus

– Actual value 1

(Bus

– Actual value 1)

0 ... 12 (24)

{ 1 }

The return value 1 (IW1) can be set for bus control in this parameter.

SK 300E, SK 700E SK 750E

0 =
Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current
5 = Status of digital inputs and relay
6 = Actual position (only POSICON,

SK700/750E)

7 = Setpoint position (only POSICON,

SK700/750E)

8 = Setpoint frequency
9 = Error number

10 = Actual position increment

1

(only

POSICON, SK700/750E)

11 = Setpoint position increment

1

(only

POSICON, SK700/750E)

12 = BUS I/O Out Bits 0-7

SK 500E

0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs

2

6 = Actual position Low word
7 = Setpoint position Low word
8 = Setpoint frequency
9 = Error number

10 = Actual position increment Low word
11 = Setpoint position increment Low word
12 = Bus I/O Out Bits 0...7
13 = Actual position High word
14 = Setpoint position High word
15 = Actual position increment High word
16 = Setpoint position increment High word
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P405)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value ramp
21 = Actual frequency without master value slip
22 = Speed from encoder

(only possible with SK 52x/53xE and
encoder feedback)

23 = Actual frequency with slip, "Actual frequency

with slip"

24 = Master value, actual freq. with slip, "Master

value, actual freq. with slip"

NOTE:

For SK 540 and SK545E 5 actual values are available. These are all set in
parameter P543, which is divided into 5 array elements for this purpose.
Parameters P544 and P545 are not required for this inverter version.

[-01] =

Actual bus value 1

[-02] =

Actual bus value 2

[-03] =

Actual bus value 3

[-04] =

Actual bus value 4

[-05] =

Actual bus value 5

P544 (P)

Actual bus value 2

(Actual bus value 2)

except SK 54xE

0 ... 12 (24)

{ 0 }

The return value 2 (IW2) can be set for bus control in this parameter.

For setting values, see parameter (P543)

P545 (P)

Actual bus value 3

(Actual bus value 3)

except SK 54xE

0 ... 12 (24)

{ 0 }

In this parameter, the return value 3 (IW3) can be set for bus control. This is only available if P546

3 (only applies for SK 700E / SK 750E).

For setting values, see parameter (P543)

1

An indicated revolution of the motor results from 8192 encoder increments.

2

The assignment of the digital inputs in P543/ 544/ 545 = 5

Bit 0 = DigIn 1

Bit 1 = DigIn 2

Bit 2 = DigIn 3

Bit 3 = DigIn 4

Bit 4 = DigIn 5

Bit 5 = DigIn 6

Bit 6 = DigIn 7

Bit 7 = Reserved

Bit 8 = Reserved

Bit 9 = Reserved

Bit 10 = Reserved

Bit 11 = Reserved

Bit 12 = Out 1

Bit 13 = Out 2

Bit 14 = Out 3

Bit 15 = Out 4

Advertising