NORD USS and Modbus RTU Manual

72

Subject to technical amendments

BU 0050 GB-3111

3.2 Error messages

Table of possible bus-specific error messages

Display

in the ControlBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details

in

P700 / P701

E010

10.0

(Bus Timeout)

Telegram timeout, data transfer is faulty. Check P513.

Check external Bus connection.

Check bus protocol program process.

Check Bus Master.

10.2

Bus Timeout Option

Telegram timeout for external bus module,
telegram communication is faulty.

Check external connection.

Check bus protocol program process.

Check Bus Master.

10.4

Init error Option

External bus module initialisation failure

Check P746.

Bus module not correctly plugged in.

Check Bus module current supply.

10.1

System error option

External Bus module system failure

10.3

10.5

10.6

10.7

10.8

Error option

Communication error in external module
connection error/fault in external module