NORD Drivesystems BU0050 User Manual

Page 36

Advertising
background image

NORD USS and Modbus RTU Manual

36

Subject to technical amendments

BU 0050 GB-3111

1.5.3.7

Actual value 1 (IW1)

The actual value 1, i.e. the actual output frequency of the inverter, is transferred as a 16 Bit value as
standard in the actual value 1. The actual value 1 is transferred to the master in the inverter response
telegram as the second word in the process data area.

PZD1

PZD2

PZD3

PZD4

ZSW

IW1

IW2/3

IW3/2

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

The actual value 1 is transferred as a whole number in the range (-32768 to 32767). In addition to the actual
frequency, other actual inverter values can be transferred. The setting is made in P543 'Actual value 1
function
'.


The settings „Actual frequency‟, „Actual speed‟, „Current‟ and „Torque current‟ are transferred as percentages
of the respective nominal values. The value 16384 (4000 HEX) corresponds to 100%. The value C000 HEX
corresponds to -100%. Actual values in the range

–200% to +200% can be transferred.


With the setting „Digital I/O status‟, the states of the control terminals and the relay (MFR) /digital outputs can
be transferred:

SK 700E/750E

Bit

Status

Bits 0-5

Digital input 1-6

Bits 6-11 for POSICON special extension unit

Digital input 7-12

Bit 6 for encoder special extension unit

Digital input 7

Bits 12-15

Multifunctional relay 1-4

SK 500E

Bit

Status

Bits 0-4

Digital input 1-5

Bits 5-6 (above SK 520E)

Digital input 6-7

Bits 12-15

Relay and digital outputs 1 - 4

With the setting 'Actual position' and 'Setpoint position' the actual absolute position is transferred. The
resolution is 1 = 0.001 revolutions.

If with SK 700E/750E the value 'Setpoint position 32 Bit' is set in parameter P546 (Setpoint function 1), then
the actual value (setpoint or actual position) is also transferred as a 32 Bit value in PZD2 and PZD3:

PZD1

PZD2

PZD3

PZD4

ZSW

IW1

IW2

1.5.3.8

Actual value 2 and actual value 3 (IW2/3)

It is possible to forward two more actual values to the controller if PPO type 2 or 4 is used for transfer.

The assignment of the actual values 2 and 3 to the process data words PZD3 and PZD4 is carried out in the
same way as the assignment of setpoints 2 and 3. These also differ in sequence between the SK 500E and
other inverter series.