NORD USS and Modbus RTU Manual

68

Subject to technical amendments

BU 0050 GB-3111

2.6 Exception Responses

If a query by the Modbus Master cannot be answered correctly, an error message is sent instead of the normal
response. The error message is structured as follows:

Slave

Master

Function Code

1 Byte

0x80 + Function code of the Master query

Exception Code

1 Byte

0x01 to 0x06

Exception Code

Description

01h

A function code has been sent, which is not supported by the FI.

02h

The telegram which has been sent is too long.

For read queries, the data range to be read out is too large.

The queried parameter is not known.

The parameter sub-index is not known.

03h

An incorrect data content has been transmitted in the function "Write Single Coil".

The number of parameters is above the limit set by Modbus.

04h

Error in access to the parameter database of the FI.

The number of coils to be written in the function "Write Single Coil" has been

exceeded

06h

The Slave is still occupied with current query and cannot receive a new order.

Example:

Parameter P102, parameter set 2 is written with the value 0x0123.

Query (Master

Slave)

Response (Slave

Master)

Address

0x08

Address

0x08

Function Code

0x06

Function Code

0x06

Address High

0x19

Address High

0x19

Address Low

0x81

Address Low

0x81

Parameter value High

0x01

Parameter value High

0x01

Parameter value Low

0x23

Parameter value Low

0x23

CRC High

0x9E

CRC High

0x9E

CRC Low

0x6E

CRC Low

0x6E

2.7 Watchdog

Modbus communication can be monitored via the parameter P513. Monitoring is started with the first valid
telegram. If the FI does not receive a new telegram within the time set in P513, error 10.0 is triggered in the FI.