NORD USS and Modbus RTU Manual

30

Subject to technical amendments

BU 0050 GB-3111

1.5.3.3

Control word (STW)

The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E

(hex)

.

PZD1

PZD2

PZD3

PZD4

STW

SW1

SW2/3

SW2/3

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Bit

Value

Meaning

Comments

0

0

OFF 1

Reverse with the brake ramp, with disconnection from supply at f=0Hz

1

ON

Ready for operation

1

0

OFF 2

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled.

1

Operating condition

OFF 2 is cancelled

2

0

OFF 3

Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition.

1

Operating condition

OFF 3 is cancelled

3

0

Disable operation

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.

1

Enable operation

The output voltage is enabled; ramp to the existing setpoint

4

0

Lock ramp generator

Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains
in the operation enabled state.

1

Operating condition

Enable ramp generator

5

0

Stop ramp generator

The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).

1

Enable ramp generator Enable setpoint on ramp generator

6

0

Disable setpoint

Selected setpoint value is set to zero on the ramp generator.

1

Enable setpoint

Selected ramp generator setpoint is activated.

7

0

No acknowledgement

With the switch from 0 to 1, errors which are no longer active are acknowledged.

1

Acknowledge

Note: When a digital input has been programmed for the "ack.fault" function, this
bit must not permanently be set to 1 via the bus (otherwise, edge evaluation
would be prevented).

8

0

1

Bit 8 active

Bus bit 8 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).

9

0

1

Bit 9 active

Bus bit 9 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).

10

0

PZD invalid

The transmitted process data is invalid.

1

PZD valid

Valid process data is transferred from the master.
Note:If setpoints only are transferred via the bus, this bit must be set so that the
transferred setpoint is valid.

11

0

1

Rotational direction:
right

Rotational direction right (priority) ON*

12

0

1

Rotational direction:
left

Rotational direction left ON*

13

0/1

Reserved

14

0/1

Bit 0 to switch
parameter set

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15

0/1

Bit 1 to switch
parameter set

* If Bit 12=0, then "Direction of rotation right ON" applies

Table 14