5 transfer procedure, 6 start pause time – NORD Drivesystems BU0050 User Manual

Page 21

Advertising
background image

1.3 USS - Protocol speciication

BU 0050 GB-3111

Subject to technical amendments

21

1.3.5

Transfer Procedure

The USS protocol functions according to the master/slave principle, whereby the master is the control device
(PC, SPS etc) and the slaves are the frequency inverters

Only one slave can be addressed with each telegram (exception: broadcast telegram without response by
the slaves).

In order to ensure reliable detection of the start of the telegram by the slave, the master must observe a so-
called start pause between the receipt of the slave telegram and transmission of the next telegram. The
master starts to transmit a telegram. After the data package has been sent, the master switches the bus data
direction from transmission to reception. The slave addressed in the telegram must respond within a
specified response time.

The lengths of the master and slave telegrams are the same, i.e. the master telegram determines the length
of the response by the slave.

Telegram traffic can be cyclical a acyclical.

The following time definitions must be observed:

Time

Size

Meaning

t

SP

Minimum 2 character durations*

Start pause time

t

AVZ

Maximum 20 ms

Response Delay Time

t

TLZ

1.5 x consecutive telegram duration

= 1,5 x (n+4) x character duration

Max. residual telegram duration

t

ZVZ

Smallest start pause time

Character delay time

*Character duration = 11 x (1/Baud rate)

1.3.6

Start Pause Time

The start character STX (= 02 Hex) on its own is not sufficient to enable the slaves to uniquely identify the
start of a telegram, because the bit combination 02/Hex may also occur in the information characters.
Therefore, in advance of the STX a start pause time t

SP

where no characters are sent for at least the

duration of 2 characters is specified for the master. The start pause time is a component of the order
telegram. A valid telegram is only identified by an STX with a preceding start pause.

The exchange of data is always performed according to the pattern described above (semi-duplex
operation):

The minimum start pause time which is to be observed for the various baud rates can be found in the Master
Telegram Time table in the Additional Information section.

Master

BCC

LGE ADR 1.

n

BCC

STX

STX LGE ADR 1.

n

BCC

t

SP

t

AVZ

STX

t

SP

t

TLZ

Slave

x

x+1

t

ZVZ