NORD Drivesystems BU0050 User Manual

Page 52

Advertising
background image

NORD USS and Modbus RTU Manual

52

Subject to technical amendments

BU 0050 GB-3111

Parameter

Setting value / Description / Note

Comments

P509

Interface

(interface)

SK 300E, SK 700E, SK 750E

0 ... 21

{ 0 }

Selection of the interface from which the inverter is controlled.

0 = Control terminal or keyboard control with the Control Box (option) ,the ParameterBox

(option) or the Potentiometer option

1 = Control terminals only, the inverter can only be controlled via the 4 digital inputs and the

analog input.

2 = USS setpoint, the frequency setpoint is transferred via the USS protocol. Control via the

digital inputs is still active.

3 = USS control word, the control signals (enable, direction of rotation, ...) are transferred via

USS, the setpoint via the analog input or the fixed frequencies.

4 = USS, all control data is transferred via the USS protocol. The analog input and the digital

inputs have no function (except safety functions, see below)

5 =

P509

Control word source

(Control word source)

SK 5xxE

0 ... 10

{ 0 }

Selection of the interface via which the FI is controlled.

0 = Control terminal or keyboard control with the Control Box (if P510=0), the

ParameterBox (not extension parameter box) or via BUS I/O Bits.

1 = Only control terminals , the FI can only be controlled via the digital and analog inputs or

via the bus I/O Bits.

2 = USS control word: the control signals (enable, direction of rotation, ...) are transferred via

the RS485 interface. The setpoint is transferred via the analog input or the fixed
frequencies.
Above SK 540E this setting should also be selected if communication via Modbus RTU is
intended. The frequency inverter automatically detects whether this is a USS protocol or a
Modbus protocol.

3 =

P510

Aux. setpoint interface

(Auxiliary setpoints interface)

SK 700E, SK 750E

0 ... 8

{ 0 }

Selection of the interface from which the inverter is controlled.

0 = Auto: The auxiliary setpoint value is automatically

taken from the interface of the main setpoint value
P509 >interface<

1 = USS

2 = CANbus

3 = Profibus

4 = InterBus

5 = CANopen

6 = DeviceNet

7 = Reserved

8 = CAN Broadcast

P510

... [-01]

... [-02]

Setpoints source

(Setpoints source)

SK 5xxE

0 ... 10

{ 0 }

Selection of the setpoint source to be parameterised.

[-01] = Main setpoint source

[-02] = Auxiliary setpoint source

Selection of the interface via which the FI receives the setpoint.

0 = Auto: the source of the auxiliary

setpoint is automatically derived from
the setting in the parameter P509
>Interface<

1 = Control terminals, digital and analog

inputs control the frequency, including
fixed frequencies

2 = USS (or Modbus RTU above SK 540E)

3 = CAN

4 = Profibus

5 = InterBus

6 = CANopen

7 = DeviceNet

8 = EtherCAT

9 = CAN Broadcast

10 = CANopen Broadcast