1.2 USS - Modules

BU 0050 GB-3111

Subject to technical amendments

15

1.2.2.5

USS Customer Interface

(SK CU1-USS, Option)

In addition to data connections, the USS customer units are also
equipped with conventional digital inputs and outputs.

Via the existing relay contacts, a mechanical motor brake can be
controlled or readiness for operation can be communicated to a
higher level system.

The digital input has a 2.5V switching threshold for the evaluation
of the temperature sensor. The input can, however, also be used
for an emergency stop function.

Connector

Functions

Maximum cross-section

Parameter

X4.1

Output relay

1,5 mm

2

P434 ... P436

X4.2

Digital input

1,5 mm

2

P420

X4.3

Data cables

1,5 mm

2

P503 ... P548
























NOTE: All control voltages are based on a common reference potential!

Potentials AGND /0V and GND /0V are internally linked in the device.

The maximum total current 5/15V is 300mA!

X

4

.1

X

4

.2

X

4

.3

01 REL1.1

02 REL1.2

41 VO +5V

40 GND /0V

73 RS485+

74 RS485-

21 DIG IN 1

42 VO +15V

Data cables:

RS485
(

terminal

73-74, RS485 +/-)

Control signal: 2.5 ... 33V

Output relay:
Max. 2.0A
28V DC /230 V AC

Digital input

1 (P420)

Voltage supply: 15V

USS

USS termination resistor

not connected

connected

ON

OF

F