NORD USS and Modbus RTU Manual

44

Subject to technical amendments

BU 0050 GB-3111

1.6.2

Switch-on block

Standby

A frequency inverter with the USS address 0 is to be switched from the status "Switch-on disabled"
(STW Bit 0

– 0), which is active when the device is switched on, to the "Standby" status (STW Bit 0 = 1).

Parameter set 1 is valid and no parameter data is transfered.

Procedure:

Check last status word (ZSW 0A 70)

Set address (Address 00)

Generate control word (STW 04 7E)

Send telegram

Check response telegram (ZSW 0B 31)

Details:

The status word of frequency inverter

is in switch-on block status

Byte No.

0

1

2

3

4

5

6

7

8

9

10

11

12

13

Meaning

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

ZSW

ZSW

IW1

IW1

BCC

Hexadecimal

02

0C

00

00

00

00

00

00

00

0B

70

00

00

75

Bit

Value Value

HEX

Meaning

15

0

0

Parameter set Bit 1 off

14

0

Parameter set Bit 0 off

13

0

Reserved

12

0

Rotation left is off

11

1

B

Rotation right is on

10

0

Reference value undershot

9

1

Bus controller

8

1

Setpoint = actual value

7

0

7

No warning

6

1

Starting disabled

5

1

No emergency stop

4

1

Disable voltage

3

0

0

No fault

2

0

Operation disabled

1

0

Not ready for operation

0

0

Not on standby

To switch the frequency inverter to the standby status, the following telegram must be sent:

0

1

2

3

4

5

6

7

8

9

10

11

12

13

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

STW

STW

SW1

SW1

BCC

02

0C

00

00

00

00

00

00

00

04

7E

00

00

74

Abbreviations used:

PKW

Parameter identifier Value

PZD

Process data

PKE

Parameter identifier

IND

Index

PWE

Parameter Value

STW

Control word 1

ZSW

Status word 1

SW1..3

Setpoint

IW1..3

Actual value