Shutdown parameters screen – HP Tower Uninterruptible Power System User Manual

Page 59

Advertising
background image

Configuration and operation 59

Shutdown Parameters screen

Click Shutdown Parameters in the menu tree to display the Shutdown Parameters screen. This screen is

available to both HPPP Administrators and Clients and allows an administrator to configure how HP Power

Protector should shut down and restart the UPS and attached devices in the event of a power failure.

Verify the Power source configuration information provided. The power source must be configured before

shutdown parameters can be configured. To configure the power source, see "Device Discovery screen (on

page

50

)".

To enter shutdown parameters:

1.

Double-click the Shutdown Configuration entry, or click Edit shutdown configuration. The Edit shutdown
configuration screen appears.

2.

In the Shutdown initiated after (sec) field, enter the number of seconds that should elapse from the time
of a utility power failure until the UPS shutdown sequence is initiated. Record the longest time of all HPPP

Clients for a UPS configuration. Configure a Shutdown initiated after time that is equal to or greater

than the longest HPPP Client time in the HPPP Administrator.