Configuration and operation 62
Upon reset, the value defaults to the maximum value of 99999 seconds.
•
The Operating system shutdown time value entered for the HPPP Administrator must be equal to or
greater than the HPPP Client configured with the greatest operating system shutdown time.
•
After the operating system shutdown begins, the shutdown process cannot be canceled, even if utility
power is restored.
•
For load shedding, each Client shuts down based on the delay settings for that Client. This increases the
backup time for the remaining Clients.
•
The UPS powers down after all load segments power down.
•
If any other condition happens during the initiated shutdown, such as the battery capacity is under limit,
the HPPP Administrator sends a shutdown command to all Clients to start the shutdown process earlier.
The following example shows the shutdown parameters for a UPS with two load segments, one connected
server that has HPPP Administrator installed, and three connected servers that have HPPP Clients installed on
each server.
Item
Description
1
Utility failure
2
Utility restore
3
Utility
4
Client 1 on load segment 1
5
Client 2 on load segment 1
6
Load segment 1
7
Client 3 on load segment 2
8
Administrator on load segment 2
9
Load segment 2
10
UPS
On utility
On battery (Shutdown initiated after)
Operating system shutdown time