HP Tower Uninterruptible Power System User Manual

Page 84

Advertising
background image

Configuration and operation 84

Configuring the redundantly powered HPPP Client power source

To configure the power source of redundantly powered HPPP Clients:

1.

Open the HPPP Client web interface.

2.

Select Settings, and then select Device Discovery.

3.

Select a redundant power source from the Node List, and then click Configure power source.
The Powersource Configuration screen appears.

4.

Enter values in the Source #1 configuration fields, and then select the Is this machine protected by
redundancy check box.

5.

Enter values in the Source #2 configuration fields, and then click Save.

6.

Select Settings and Shutdown Parameters, and then select Edit shutdown configuration.

7.

Enter a value in the Shutdown initiated after (sec) field.

IMPORTANT:

A Client Shutdown initiated after value of none automatically sets the shutdown

value of any UPS Network Modules to the default 99999 seconds upon reset. In this

configuration, UPS devices power down as late as possible without performing a graceful

shutdown.

To configure graceful shutdowns, enter the value for the Client, reset the system, and then enter a value
in the Shutdown initiated after (sec) field of any UPS Network Modules.
The Client uses the greatest value of any configured HPPP devices to perform a graceful shutdown when
one of the redundant UPS devices goes on battery.