Ups output specifications, Environmental specifications – HP Parallel Uninterruptible Power System User Manual

Page 103

Advertising
background image

Specifications 103

UPS output specifications

3 Phase UPS NA

3 Phase UPS INTL

Nominal output voltage

120/208 Vac three-phase

230/400 Vac three-phase

Output voltage variation

(standard)

108-132 Vac phase to neutral

187-255 Vac phase to neutral

187-229 Vac phase to phase

324-441 Vac phase to phase

Output voltage variation
(reduced)

108-132 Vac phase to neutral

207-253 Vac phase to neutral

187-229 Vac phase to phase

358-438 Vac phase to phase

Output receptacles on
standalone UPSs—12kVA

models

Output module (2x L15-30R)

Output module (2x IEC 309-16 A, 5

wire)

Output receptacles on
standalone UPSs—8kVA

1x L15-30R

1x IEC 309-16 A, 5 wire

Short circuit capability
(Battery Mode)

84 A, <300 ms

44 A, <300 ms

Short circuit capability

(Normal Mode)

Limited by 50 A input breaker (30 A

source on 8kVA models)

Limited by 30 A input breaker (16 A

source on 8kVA models)

Nominal output frequency

50-60 Hz auto-detection (Normal
Mode)

50-60 Hz auto-detection (Normal
Mode)

50 or 60 Hz (Battery Mode)

50 or 60 Hz (Battery Mode)

Output frequency variation

Synchronized (Normal Mode)

Synchronized (Normal Mode)

±0.1 when not synchronized with

source (Battery Mode)

±0.1 when not synchronized with

source (Battery Mode)

Output overload

100-110%: load transfers to

Auto-Bypass Mode after 10 minutes

100-110%: load transfers to

Auto-Bypass Mode after 10 minutes

110-125%: load transfers to

Auto-Bypass Mode after 1 minute

110-125%: load transfers to

Auto-Bypass Mode after 1 minute

125-150%: load transfers to

Auto-Bypass Mode after 5 seconds

125-150%: load transfers to

Auto-Bypass Mode after 5 seconds

>150%: load transfers to Auto-Bypass
Mode after 300 ms

>150%: load transfers to Auto-Bypass
Mode after 300 ms

Voltage waveform

Normal Mode and Battery Mode:

Sine wave; <2% THD with linear load;
<5% with nonlinear load

Normal Mode and Battery Mode:

Sine wave; <2% THD with linear load;
<5% with nonlinear load

Full output

Three-phase

Three-phase

Environmental specifications

Feature

Specification

Operating
temperature

0°C to 40°C (32°F to 104°F)

Optimal battery performance: 5°C to 25°C (41°F to

77°F)

Storage temperature 0°C to 25°C (32°F to 77°F)
Transit temperature

-25°C to 55°C (-13°F to 131°F)