Mode transfers, Redundant signal wiring, Auto-identification – HP Parallel Uninterruptible Power System User Manual

Page 78

Advertising
background image

Communication 78

Mode transfers

If one UPS in a parallel system transfers from High Efficiency mode (on page

65

) to Normal mode (on

page

65

), the other UPSs transfer also.

If one UPS transfers to Battery mode (on page

66

), the remaining UPSs in the parallel system stay online.

The transferred UPS might transfer back to online at any time, and the parallel system resynchronizes.

When a parallel system is on battery power , the front panels of each UPS display the battery status
information of the UPS with the lowest runtime remaining. When the first UPS shuts down, the other UPSs

also shut down.

In a parallel system configured for redundancy, the UPSs use a distributed bypass, and the following
alarms cause an individual UPS to power down instead of transferring to Auto-Bypass mode (on page

66

):

o

Failure of the fan, fuse, temperature sensor, or power supply

o

Inverter AC under voltage

o

Battery current limit

o

DC line under voltage

o

Battery over voltage

Redundant signal wiring

The redundant signal wiring provides redundant backfeed protection in case of Parallel UPS Card failure in
the parallel system. If the card fails, the UPSs transfer to Normal mode (on page

65

). The system runs

unsynchronized, and any UPS can transfer to Battery mode (on page

66

) as necessary. If any UPS must

transfer to Auto-Bypass mode (on page

66

), the redundant signal wiring allows the entire parallel system to

transfer to Auto-Bypass mode, without backfeeding.

Auto-identification

The UPS parallel system automatically assigns identities to each UPS in the system. To take advantage of this

feature, wire the Parallel UPS Cards together. For more information, see "Installing in a parallel configuration
(on page

26

)."

Upon powering up the UPS, the UPS with the initializing jumper installed identifies itself as UNIT 1. The next

UPS wired identifies itself as UNIT 2, and so forth. The auto-identification sequence takes about 15-20

seconds to complete after all the UPSs in the parallel system have logic power.
If a UPS is powered down or otherwise loses logic power, the UPS re-identifies itself in the proper sequence
after logic power is restored.
If a UPS is powered down and removed from the parallel system, the other UPSs in the system do not

re-identify themselves to compensate for the missing UPS until logic power to all the UPSs is cycled. For

example, if you remove UNIT 2 and rewire UNIT 3's Parallel UPS Card IN port to UNIT 1's Parallel UPS Card
OUT port, UNIT 3 does not re-identify itself as UNIT 2 until logic power is cycled. The Parallel UPS Cards for

UNIT 1 and UNIT 3 continue to function normally without the need to re-identify.