Troubleshooting 94

Troubleshooting

LED and audible alarm troubleshooting

This UPS is designed for durable, automatic operation and also alerts you whenever potential operating
problems might occur. Usually the alarms shown on the control panel do not mean that the output power is

affected. Instead, they are preventive alarms intended to alert you of a possible condition.
The following table describes typical alarms and conditions. If an alarm appears with a service code, contact

HP technical support ("

HP contact information

" on page

107

).

To check the Event Log for a list of active alarms:

1.

Press any button on the front panel display to activate the menu options.

2.

Press the down arrow button until EVENT LOG displays.

3.

Press the right arrow button to display the list of alarms and conditions.

Alarm

LED

On Battery

LED

Power On

LED

Auto-Bypass

LED

Audible alarm Condition

On

UPS is in Normal
mode (on page

65

).

Flashing

A new message is
active.

On

On—1 beep

every 5 seconds

On Battery ("

UPS is

on battery

" on

page

100

)

On

On—Continuous
for 10 seconds

Battery Low
("

Battery low

condition

" on page

96

)

On

On—1 beep

every 3 seconds

Battery Breaker (on

page

95

)

On

On—1 beep

every 3 seconds

On Bypass ("

UPS is

on bypass

" on

page

100

)

Flashing

On—1 beep

every 1 seconds

Bypass

Unavailable

("

Bypass is

unavailable

" on

page

96

)

On

On—1 beep
every 3 seconds

Battery Connection
("

Battery

connection

condition

" on page

96

)