UPS installation 38

Connecting devices to the UPS

CAUTION:

Do not plug laser printers into the UPS output receptacles. The instantaneous current

drawn by this type of printer can overload the UPS.

Before connecting devices, verify that the UPS will not overload by checking that the ratings of the devices do

not exceed the UPS capacity. If the equipment rating is listed in amps, multiply the number of amps by the

nominal AC source to determine the VA.
To provide additional receptacles:

For the 8kVA models—Plug a PDU into the UPS output receptacle at the end of the power cord.

For the 12kVA models—

a.

Install the included output module on the rear rack frame.

b.

Plug the output module into the special UPS output receptacle, located on the rear of the UPS.

Item

Description

1

Rack corner post

2

Mounting locations

3

Mounting top bracket

4

Output cord

5

Mounting bottom bracket

6

Input cord

Charging the UPS batteries

With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.

IMPORTANT:

Charge the batteries for at least 48 hours before supplying backup power to

devices. The batteries charge to:

80 percent of their capacity within 5 hours

100 percent of their capacity within 48 hours