Battery specifications, Battery runtimes – HP Parallel Uninterruptible Power System User Manual

Page 104

Advertising
background image

Specifications 104

Feature

Specification

Relative humidity

Operating: 5% to 95%; noncondensing

Non-operating: 5% to 95%; 38.7°C (101.7°F)

maximum wet bulb temperature with no cosmetic
damage

Operating altitude

Up to 1,000 m (3,300 ft) above sea level

Up to 2,000 m (6,600 ft) with 1% derating per + 100 m

(330 ft)

Transit altitude

UP to 15,000 m (49,000 ft) above sea level

Heat dissipation

1432 BTU/hr maximum at 100% rated load (High

Efficiency Mode)

4094 BTU/hr maximum at 100% rated load (Standard

Mode)

Audible noise

Less than 58 dBA at 1 meter typical (Normal Mode)

Less than 64 dBA at 1 meter typical (Battery Mode)

Leakage current

<3.5 mA

Surge suppression

ANSI C62.41 Category B3

Safety conformance 3 Phase UPS NA: UL 1778 4th edition; CSA C22.2,

No. 107.1 and No. 107.3

3 Phase UPS INTL: EN 60950-1 and IEC 62040-1-1

Agency Markings

3 Phase UPS NA: UL/cUL

3 Phase UPS INTL: CB, CE, GS, Ctick, GOST, BSMI

EMC (Class A)

3 Phase UPS NA: FCC Part 15, ICES

3 Phase UPS INTL: EN 62040-2

Battery specifications

Feature

Specification

Configuration

UPS internal batteries: (40) 12 V, 5 Ah

+1 ERM: (20) 12 V, 9 Ah

+2 ERMs: (40) 12 V, 9 Ah

+3 ERMs: (60) 12 V, 9 Ah

+4 ERMs: (80) 12 V, 9 Ah

Type

Each model contains maintenance-free, sealed,

valve-regulated lead-acid batteries.

Monitoring

Advanced monitoring for earlier failure detection and

warning

Charging

8-10 times the discharge time. Complete charge takes no
more than 48 hours. Approximately 5 hours to 80 percent

capacity at default nominal utility voltage and no load.

Battery runtimes

Battery runtimes are approximate and vary depending on the load configuration and battery charge.