Setting the battery low alarm level – HP Parallel Uninterruptible Power System User Manual

Page 70

Advertising
background image

UPS operations 70

Description

Available settings

Default setting

Delay

Site Wiring Fault Notice

[Enabled][Disabled]

Enabled

Reset Custom Event Settings

0 through 32

Total: 0/32

REPO Configuration

[Enabled][Disabled]

Enabled

Setting the Battery Low alarm level

The default Battery Low alarm level setting provides approximately 2.5 minutes of battery warning for a UPS.

Additional ERMs installed in a parallel system can provide a longer warning time.
To set the Battery Low Alarm Level:

1.

Press any button to activate the menu options.

2.

Select SETTINGS > USER SETTINGS > BATTERY SETUP > Automatic Battery Tests.

3.

Use the up or down arrow buttons to select the volts per cell. For a list of settings, see the table below.

4.

Press the left arrow button to save the setting.

5.

Press and hold the ESC button until the Start screen appears.

Warning time

(in minutes)

Number of ERMs

installed

Battery Low Alarm Level (user setting)

20% Load

50% Load

100% Load

2

1

1.783

1.821

1.854

2

2

1.776

1.811

1.831

2

3

1.772

1.798

1.818

2

4

1.768

1.781

1.805

3

1

1.805

1.848

1.981

3

2

1.793

1.833

1.859

3

3

1.787

1.820

1.843

3

4

1.781

1.803

1.831

4

1

1.822

1.868

1.918

4

2

1.807

1.850

1.883

4

3

1.789

1.836

1.866

4

4

1.793

1.818

1.850

5

1

1.835

1.884

1.941

5

2

1.818

1.863

1.903

5

3

1.799

1.849

1.883

5

4

1.803

1.823

1.865

Values are approximate.