Replacing the erm – HP Parallel Uninterruptible Power System User Manual

Page 90

Advertising
background image

Maintenance 90

2.

Power down the UPS.

o

Standalone UPS configuration—See "Powering down the standalone UPS (on page

72

)."

o

Individual UPS in a parallel configuration—See "Powering down an individual paralleled UPS (on
page

72

)."

o

Parallel UPS configuration—See "Powering down the parallel system (on page

73

)."

3.

Switch the circuit breaker for any attached ERMs to the Off (down) position ("

Switching off the ERM

circuit breaker

" on page

59

).

4.

Switch the battery circuit breaker for the UPS to the Off (down) position.

5.

Unplug the UPS power cord.

6.

Disconnect the communications cable from the option card.

7.

Disconnect the ground bonding cable.

8.

Disconnect the REPO port.

9.

Unplug the load devices.

10.

Unplug all connected extension bars and PDUs.

11.

Unplug the ERM connected to the UPS.

12.

Remove the UPS front bezel ("

Removing the UPS front bezel

" on page

81

).

13.

Remove the UPS battery bracket ("

Removing the UPS battery bracket

" on page

19

).

14.

Remove the UPS battery modules.

15.

Remove the screws securing the UPS to the rack.

16.

Remove the UPS from the rack.

To replace the component, reverse the removal procedure.

Replacing the ERM

To remove the ERM:

1.

Switch the circuit breaker for any attached ERMs to the Off (down) position ("

Switching off the ERM

circuit breaker

" on page

59

).