Control terminals, Relay output contacts – HP Parallel Uninterruptible Power System User Manual

Page 76

Advertising
background image

Communication 76

Pin number Signal name Function

Direction from the UPS

4

No connection

5

GND

Signal common (tied to chassis)

6

No connection

7

No connection

8

No connection

9

No connection

Control terminals

The cables should be connected to the control terminal with a mating connector. Input and output terminals

have a functional isolation from terminal to terminal. They are connected to the UPS chassis through
individual 1 M

W

resistors.

If using a semiconductor switch type, pay attention to the proper polarity. A relay or other mechanical control

is preferred.

Relay output contacts

WARNING:

The relay output contacts must not be connected to any utility connected circuits.

Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of

30 VAC/1 A and 60 Vdc/2 A nominal values.