Powering down the standalone ups, Powering down an individual paralleled ups – HP Parallel Uninterruptible Power System User Manual

Page 72

Advertising
background image

UPS operations 72

CAUTION:

If the polarity is reversed while connecting the REPO port, the UPS powers up

normally.

2.

Power up the UPS.

o

Standalone UPS configuration—See "Powering up the standalone UPS (on page

25

)."

o

Parallel UPS configuration—See "Powering up the parallel system (on page

39

)."

3.

Verify proper connection of the REPO port:

a.

Disconnect the REPO port.

b.

Reconnect the REPO port.
If the polarity is correct, the REPO connectors can be disconnected, and then reconnected, without
initiating a REPO.

c.

Verify that the UPS remains in Normal mode (on page

65

).

d.

If a REPO is initiated, the polarity is reversed. Check and correct the connections.

Powering down the standalone UPS

1.

Switch the output circuit breaker to the Off position.

2.

Press any button on the front panel display to activate the menu options.

3.

Select TURN UPS ON/OFF, TURN UPS OFF, and press the right arrow button.

4.

Confirm the selection. Press and hold the right arrow button for three seconds, until the UPS stops
beeping.
The output relays open, the UPS transfers to Standby mode (on page

64

), and the Power On LED turns

off.

5.

Switch the UPS battery circuit breaker to the Off position.

6.

If optional ERMs are installed, switch all ERM battery circuit breakers to the Off position.

7.

Switch the UPS input circuit breaker to the Off position.

8.

Press ESC until the HP logo appears.

9.

Disconnect the UPS from utility power.

Powering down an individual paralleled UPS

1.

Switch the output circuit breaker to the Off position.

2.

Press any button on the front panel display to activate the menu options.

3.

Select the TURN UPS ON/OFF, TURN UPS OFF, and press the right arrow button.

4.

Confirm the selection. Press and hold the right arrow button for three seconds, until the UPS stops

beeping.
The output relays open, the UPS transfers to Standby mode, and the Power On LED turns off.

5.

Switch the UPS battery circuit breaker to the Off position.

6.

If optional ERMs are installed, switch all ERM battery circuit breakers to the Off position.

7.

Switch the UPS input circuit breaker to the Off position.

8.

Press ESC until the HP logo appears.

Advertising