Connecting the repo port, Connecting to a normally-open contact – HP Parallel Uninterruptible Power System User Manual

Page 30

Advertising
background image

UPS installation 30

The ground bonding cable is not included.

Connecting the REPO port

This UPS has two REPO ports, normally-open and normally-closed. Before connecting to a REPO port, review

and observe all warnings.

WARNING:

The pins on the REPO port are polarity sensitive. Be sure to verify polarity while

connecting the REPO port in parallel with other HP UPSs.

WARNING:

To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a

UPS installed in a computer equipment room must be connected to a REPO circuit.

NOTE:

Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or

equivalent).

HP recommends using different colors for the positive and negative wires.
To avoid inadvertant EPO:

Minimize wire strain while connecting the REPO port.

Avoid allowing the wires to hang in the rear of the UPS.

Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS.

For more information about the REPO port, see "REPO port (on page

10

)" .

For information about verifying the REPO connection, see "Verifying the REPO port connection (on page

71

)"

.

Connecting to a normally-open contact

IMPORTANT:

The remote switch must be in the open position to enable power to the UPS output.